| Notes |
| Date |
Text |
| 2005-07-14 00:00:00 | ELEC FOR REVIEW. | | | REDLINED THE FOLLOWING. | | | | | | PLEASE SEE MISSING EQUIPMENT GROUNDING | | | CONDUCTOR FROM MAIN TO POOL SUB PANEL. | | | 250.110,250.122 ETC | | | | | | POOL PUMP, 125% FOR CONTINUOUS LOAD.(3 | | | OR MORE HOURS). | | | | | | THERE IS NO NEED FOR CORRECTIONS, | | | HOWEVER OF PLANS ARE REVISED FOR JOBSITE | | | CHANGES, PLEASE MAKE THE ABOVE | | | CORRECTIONS/ADJUSTMENTS AT THAT TIME. | | | |
|