Plan Review Notes For Permit 05070030
Permit Number 05070030
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-14 00:00:00ELEC FOR REVIEW.
 REDLINED THE FOLLOWING.
  
 PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTOR FROM MAIN TO POOL SUB PANEL.
 250.110,250.122 ETC
  
 POOL PUMP, 125% FOR CONTINUOUS LOAD.(3
 OR MORE HOURS).
  
 THERE IS NO NEED FOR CORRECTIONS,
 HOWEVER OF PLANS ARE REVISED FOR JOBSITE
 CHANGES, PLEASE MAKE THE ABOVE
 CORRECTIONS/ADJUSTMENTS AT THAT TIME.
  