Plan Review Notes
Plan Review Notes For Permit 05070029
Permit Number 05070029
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-15 00:00:00*********** UNSAT ************
  
 1)NOTE: PLEASE SEE PLANS ARE TO BE
 SIGNED BY THE ARCHITECT OF RECORD AND
 SHALL MATCH WITH SIGNATURE ON FILE.
 FS 481.221
 ONE COPY OF PLANS RETAINED AND SHALL BE
 RETAINED WITH SAID FILE.
  
 2)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO POOL
 PANEL.
 250.110,250.122 ETC.
  
 3)NOTE: PLEASE SEE CONTINUOUS LOADS ON
 POOL PANEL ARE TO BE SHOWN AT 125%.
 (POOL PUMP).
  
 4)NOTE: PLEASE SEE RECEPTS MISSING ALONG
 COUNTERSPACE PER 210.52C1 OUTSIDE WALL
 AND CORNER WALL.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW, IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-07-14 00:00:00IN ELEC FOR REVIEW.