| Plan Review Notes For Permit 05070029 |
| Permit Number |
05070029 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-15 00:00:00 | *********** UNSAT ************ | | | | | | 1)NOTE: PLEASE SEE PLANS ARE TO BE | | | SIGNED BY THE ARCHITECT OF RECORD AND | | | SHALL MATCH WITH SIGNATURE ON FILE. | | | FS 481.221 | | | ONE COPY OF PLANS RETAINED AND SHALL BE | | | RETAINED WITH SAID FILE. | | | | | | 2)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR FROM MAIN TO POOL | | | PANEL. | | | 250.110,250.122 ETC. | | | | | | 3)NOTE: PLEASE SEE CONTINUOUS LOADS ON | | | POOL PANEL ARE TO BE SHOWN AT 125%. | | | (POOL PUMP). | | | | | | 4)NOTE: PLEASE SEE RECEPTS MISSING ALONG | | | COUNTERSPACE PER 210.52C1 OUTSIDE WALL | | | AND CORNER WALL. | | | | | | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW, IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | 2005-07-14 00:00:00 | IN ELEC FOR REVIEW. |
|