| 2005-08-03 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05070015 | | | ADD: 200 GREGORY RD | | | CONT: CARPENTER ELEC | | | TEL: (561)848-7881 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) PROVIDE INFORMATION ON SLAB AND | | | ANCHORING OF UNIT. | | | 1606.1.3 ANCHORAGE AGAINST OVERTURNING, | | | UPLIFT AND SLIDING. STRUCTURAL | | | MEMBERS AND SYSTEMS, AND COMPONENTS | | | AND CLADDING IN A BUILDING OR | | | STRUCTURE SHALL BE ANCHORED TO RESIST | | | WIND-INDUCED OVERTURNING, UPLIFT | | | AND SLIDING AND TO PROVIDE CONTINUOUS | | | LOAD PATHS FOR THESE FORCES TO THE | | | FOUNDATION.WHERE A PORTION OF THE | | | RESISTANCE TO THESE FORCES IS PROVIDED | | | BY DEAD LOAD, THE MINIMUM DEAD LOAD | | | LIKELY TO BE IN PLACE DURING A DESIGN | | | WIND EVENT SHALL BE USED. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|