| Plan Review Notes For Permit 05070015 |
| Permit Number |
05070015 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-27 00:00:00 | MECH. PLAN REVIEW: | | | | | | IF ELECT. GENERATOR IS 10 FEET FROM | | | BUILDING AND EXHAUST IS DIRECTED AWAY | | | FROM BUILDING THIS MEET INTENT OF MECH. | | | CODE. | | | 2001 FBC/M 804.3.3 TERMINATION. | | | | | | 2001 FBC/M SECTION 915 | | | REQUIREMENT OF NFPA 37 | | | 8.2.3.2 EXHAUST SYSTEM | | | TERMINATION. | | | | | | |
|