| 2005-07-26 00:00:00 | ************ UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SUBMIT SPECS /CUT SHEETS |
| | FOR ATS. |
| | |
| | 2)NOTE: PLEASE INDICATE EQUIPMENT ON THE |
| | LOAD SIDE OF ATS. PLEASE INDICATE |
| | WHEATHER OR NOT A MAIN OR MAIN CIR BRKR |
| | PANEL? |
| | 225.31, 110.27 |
| | |
| | 3)NOTE: PLEASE KNOW, ONLY GEN LT/AND |
| | RECEPT LOADS MAY TAKE DERATINGS AS |
| | PERMITTED UNDER NEC. 220.31 |
| | ALL CONNECTED APPLIANCE LOADS, MOTOR |
| | LOADS,ETC SHALL BE FIGURED AT 100%. |
| | PLEASE SEE ANY CONTINUOUS LOADS SHALL BE |
| | 125%. |
| | PLEASE SEE THAT A/C LOAD MUST BE FIGURED |
| | FOR HEAT STRIP LOAD, UNLESS MEANS OF |
| | AUTOMATIC LOAD SHEDDING IS PROVIDED. |
| | LOAD SHEDDING MAY ALSO BE PROVIDED FOR |
| | OTHER CONNECTED LOADS. |
| | GENERATOR MUST BE SIZED FOR ALL LOADS IF |
| | ATS IS PROVIDED. |
| | 702.5 |
| | |
| | 4)NOTE: PLEASE SEE FBC 104.2.1 WHICH |
| | REQUIRES THE PRINTED NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR |
| | PLANS/DESIGN. |
| | |
| | 5)NOTE: PLEASE SEE MANUFACTURE CUT SHEET |
| | FOR GENERATOR. PLEASE CLEARLY INDICATE |
| | ON BOTH SETS WHICH UNIT IS TO BE |
| | INSTALLED. |
| | |
| | 6)NOTE: PLEASE SUBMIT A DETAIL FOR SLAB |
| | AND ATTACHMENT FOR UNIT. |
| | |
| | 7)NOTE: PLEASE BE SURE THE SURVEY SHOWS |
| | THE MIN BASED FLOOD ELEVATION(BFE). |
| | PLEASE SEE THAT SLAB IS 6" ABOVE BFE. |
| | |
| | PLEASE SEE MECHANICAL REVIEW COMMENTS |
| | AND/OR NOTES PERTAINGING TO MIN |
| | CLEARNECE FROM OPEINS INTO DWELLING |
| | UNIT. |
| | |
| | PLEAS KNOW, A 4X MAY BE ACCESSED IF |
| | GENERATOR IS INSTALLED, WIRED ETC BEFORE |
| | ELECTRICLA PERMIT IS ISSUED AND POSTED |
| | ON THE JOBSITE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |