Plan Review Notes
Plan Review Notes For Permit 05070015
Permit Number 05070015
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-26 00:00:00************ UNSAT *************
  
 1)NOTE: PLEASE SUBMIT SPECS /CUT SHEETS
 FOR ATS.
  
 2)NOTE: PLEASE INDICATE EQUIPMENT ON THE
 LOAD SIDE OF ATS. PLEASE INDICATE
 WHEATHER OR NOT A MAIN OR MAIN CIR BRKR
 PANEL?
 225.31, 110.27
  
 3)NOTE: PLEASE KNOW, ONLY GEN LT/AND
 RECEPT LOADS MAY TAKE DERATINGS AS
 PERMITTED UNDER NEC. 220.31
 ALL CONNECTED APPLIANCE LOADS, MOTOR
 LOADS,ETC SHALL BE FIGURED AT 100%.
 PLEASE SEE ANY CONTINUOUS LOADS SHALL BE
 125%.
 PLEASE SEE THAT A/C LOAD MUST BE FIGURED
 FOR HEAT STRIP LOAD, UNLESS MEANS OF
 AUTOMATIC LOAD SHEDDING IS PROVIDED.
 LOAD SHEDDING MAY ALSO BE PROVIDED FOR
 OTHER CONNECTED LOADS.
 GENERATOR MUST BE SIZED FOR ALL LOADS IF
 ATS IS PROVIDED.
 702.5
  
 4)NOTE: PLEASE SEE FBC 104.2.1 WHICH
 REQUIRES THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR
 PLANS/DESIGN.
  
 5)NOTE: PLEASE SEE MANUFACTURE CUT SHEET
 FOR GENERATOR. PLEASE CLEARLY INDICATE
 ON BOTH SETS WHICH UNIT IS TO BE
 INSTALLED.
  
 6)NOTE: PLEASE SUBMIT A DETAIL FOR SLAB
 AND ATTACHMENT FOR UNIT.
  
 7)NOTE: PLEASE BE SURE THE SURVEY SHOWS
 THE MIN BASED FLOOD ELEVATION(BFE).
 PLEASE SEE THAT SLAB IS 6" ABOVE BFE.
  
 PLEASE SEE MECHANICAL REVIEW COMMENTS
 AND/OR NOTES PERTAINGING TO MIN
 CLEARNECE FROM OPEINS INTO DWELLING
 UNIT.
  
 PLEAS KNOW, A 4X MAY BE ACCESSED IF
 GENERATOR IS INSTALLED, WIRED ETC BEFORE
 ELECTRICLA PERMIT IS ISSUED AND POSTED
 ON THE JOBSITE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]