Plan Review Notes
Plan Review Notes For Permit 05061909
Permit Number 05061909
Review Stop E
Sequence Number 2
Notes
Date Text
2005-08-31 00:00:00*** UNSAT ***
  
 1)NOTE:IF ENGINEER ON PLANS IS NOT AN
 EMPLOYEE OF GARRISON DESIGN GROUP,PLEASE
 PROVIDE A SIGNED, SEALED LTR FROM
 ENGINEER WHICH STATES THIS.
 A CA/ LICENSE # IS NOT REQUIRED FOR
 GARRISON DESIGN GROUP AS THEY ARE NOT AN
 ARCHITECTUAL OR ENGINEERING FIRM TO THIS
 OFFICE'S UNDERSTANDING.
  
 2) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 PLANS DO NOTE AIC RATING FOR MAIN ,
 HOWEVER PANELS DO NOT INDICATE SERIES
 RATINGS?
  
 3)NOTE: PLEASE SEE RECEPTS MISSING PER
 210.52. PLEASE SEE THESE ARE REDLINE DON
 PLANS AT LOCATIONS.
  
 4)NOTE: PLEASE SEE SD AS SHOWN IN
 KITCHEN MAY NOT BE CLOSER THAN 20'FROM
 COOKING APPLIANCES UNLESS MEETING THE
 EXCEPTIONS PERMITTED UNDER NFPA-72
 8-1.4.2
 PLEASE SEE SD FOR MASTER BEDROOM, MUST
 BE INSIDE MASTER BEDRM AREA. NFPA-72
 8-1.4.1.6.2, AND CHAPTER 2 FOR
 PLACEMENT. 3' FROM A PEAK ON SLOPED
 CEILING AND WITHIN 12" OF CEILING ON A
 FLAT CEILING. PLEASE SEE SD IS SHOWN IN
 HALLWAY WHICH ALSO CONTAINS A HEADER
 MORE THAN 12".
 THIS WAS ALSO REDLINED ON PLANS.
  
 5)NOTE: PLEASE SEE LOAD CALCULATIONS NOW
 SUBMITTED.
 PLEASE SEE TOTALS SHOWN AND LOADS
 INDICATED IN LOAD CALCS. SOME OF THESE
 #'S DO NOT CORRELATE. PLEASE SEE THESE
 ARE REDLINED.
 PLEASE ADJUST.
 PLEASE SEE THERE ARE SOME ITEMS ON PLANS
 WHICH ARE NOT INCLUDED IN LOAD
 CALCULATIONS.
 PLEASE SEE WINE COOLER(DEDICATED?)
 PLEASE SEE 220.4 FOR LOADS OF
 RECESSEDLIGHTING. RECESSED LTS SHALL
 INDICATE THE WATTAGE OF FIXTURES IN
 ELECTRICAL LEGEND AND LOADS SHALL BE
 ABOVE GEN LTS LOADS.
  
 6)NOTE: PLEASE SEE PANEL SCHEDULE/LOAD
 CALCS INDICATE 3-GDO'S, HOWEVER ONLY TWO
 ARE SHOWN ON PLANS?
  
 7)NOTE: PLEASE SEE PANEL SCHEDULE
 INDICATES 2-DISHWASHERS? YET ONLY ONE
 COULD BE LOCATED ON PLANS? AND ONLY ONE
 ON LOAD CALCS?
 PLEASE CORRELATE.220,215.5
  
 8)NOTE: PLEASE SEE 210.70 AND LS 101/
 NFPA-101 CHAPTER 5-8.A LT FIXTURE OF
 SOME SORT WILL BE REQUIRED AT MEANS OF
 EGRESS, HALLWAYS/ STAIRWAYS. PLEASE SEE
 REDLINE DPLANS FOR LOCATIONS WHERE A MIN
 OF ONE LT FIXTURE WILL BE REQUIRED.
 PLEASE RM OFF KITCHEN, AND STAIRS WHERE
 A J-BOX IS SHOWN.
  
 9)NOTE: PLEASE CORRELATE PLANS WITH
 RISER. RISER INDICATES A METER/MAIN
 COMBO AND PLANS INDICATE A SEPARATE
 METER AND A MAIN PANEL??
 215.5
  
 10)NOTE: PLEASE PROVIDE ROOM AREA
 DESIGNATIONS ON ELECTRICAL PLANS.
  
 11)NOTE: PLEASE SEE POSSIBLE COMMENTS
 FROM PLUMB/ MEACH, WHEATHER GAS WATER
 HEATER CAN BE LOCATED IN SMAE ENCLOSED
 CLOSET WITH AHU??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESIATE IN CONTACTING THIS
 OFFICE.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]