| 2005-09-06 00:00:00 | MECH. PLAN REVIEW: | | | | | | 1. MASTER BATH REQUIRES EXHAUST FAN IN | | | AREAS TUB/ SHOWERS.2003 FBC/M | | | 402.3.1.. | | | | | | 2. GAS CLOTHES DRYER REQUIRES MANF. | | | INSTRUCTIONS FOR COMBUSTION/MAKE UP AIR. | | | 2001 FBC/M CHAPTER 7 | | | | | | 3. GAS HOT WATER HEATER, LOCATER IN | | | GARAGE CLOSIT REQUIRES COMBUSTION AIR | | | AND A/C AHU MUST BE DUCTED R/A . | | | 2001 FBC/M CHAPTER 7. | | | | | | GARAGE CLOSIT MUST HAVE ADQUIT | | | CLEARANCE TO REMOVE LARGEST PEACE OF | | | EQUIPMENT AND ADQUIT SERVICE CLEARANCE. | | | 2003 FBC/M 306.1 CLEARANCES FOR | | | MAINTENANCE AND REPLANCEMENT. | | | | | | | | | 4. RETURN AIR OUT OF SECOND FLOOR S/W | | | BEDROOM MUST BE SAME SIZE AS SUPPLY AIR | | | ON DUCTED RETURN AIR SYSTEM. | | | 2003 FBC/M 601.4 . | | | | | | 5. A/C PLANS REQUIRE TO BE | | | SIGINED/SEALED. | | | FAC 61GI - 16.002 . | | | | | | PAT RAFTER 561/805/6728 OR 805/6719 | | | PATTY KRAUSS. | | | | | | PLEASE CALL IF THEAR ANY QUESTIONS. | | | | | | |
|