Plan Review Notes
Plan Review Notes For Permit 05061909
Permit Number 05061909
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-13 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} FIRM LICENSE NUMBER MUST BE ON THE
 TITLE BLOCK PER 61G15-23.002.
  
 2} THE LOAD CALCULATION EXCEEDS THE
 SERVICE RATING, IN VIOLATION OF 230.42.
  
 3} THE PANEL SCHEDULE INDICATES A 70 AMP
 BREAKER FEEDING THE SUB PANEL, RISER
 NOTE INDICATESS A 60 AMP. THE LOAD CALC
 LISTED AT 16839/240=70.16, THE FEEDER
 WIRE IS #6. PLEASE CORRELATE.
  
 4} THE SERVICE IS SHOWN AT TWO DIFFERENT
 LOCATIONS ON THE BUILDING, PLEASE
 INDICATE ACTUAL PROPOSED CONDITIONS.
  
 5} RECEPTACLES ARE REQUIRED OUTDOORS,
 FRONT AND REAR, PER 210.52(E).
  
 6} THE A/C DISCONNECTS APPEAR TO BE
 LOCATED IN CLEARANCE VIOLATION 110.26.
  
 7} SHOW LOCATION OF AHU#2 ON PLANS, SO
 DISCONNECT, LIGHT AND RECEPTACLE
 COMPLIANCE CAN BE DETERMINED.
  
 8} UPSTAIR BATHS (NO NUMBER) MUST HAVE A
 GFI RECEPTACLE WITHIN 3' OF THE BASINS
 PER 210.52(D), 210.8(A)(1).
  
 9} ALL ROOMS UPSTAIRS WITH TH EXCEPTION
 OF THE BATH ON THE SOUTH SIDE, ARE IN
 VIOLATION OF SPACING REQUIIREMENTS OF
 210.52(A)(1)&(2). SEE REVIEWED PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  