| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} FIRM LICENSE NUMBER MUST BE ON THE |
| | TITLE BLOCK PER 61G15-23.002. |
| | |
| | 2} THE LOAD CALCULATION EXCEEDS THE |
| | SERVICE RATING, IN VIOLATION OF 230.42. |
| | |
| | 3} THE PANEL SCHEDULE INDICATES A 70 AMP |
| | BREAKER FEEDING THE SUB PANEL, RISER |
| | NOTE INDICATESS A 60 AMP. THE LOAD CALC |
| | LISTED AT 16839/240=70.16, THE FEEDER |
| | WIRE IS #6. PLEASE CORRELATE. |
| | |
| | 4} THE SERVICE IS SHOWN AT TWO DIFFERENT |
| | LOCATIONS ON THE BUILDING, PLEASE |
| | INDICATE ACTUAL PROPOSED CONDITIONS. |
| | |
| | 5} RECEPTACLES ARE REQUIRED OUTDOORS, |
| | FRONT AND REAR, PER 210.52(E). |
| | |
| | 6} THE A/C DISCONNECTS APPEAR TO BE |
| | LOCATED IN CLEARANCE VIOLATION 110.26. |
| | |
| | 7} SHOW LOCATION OF AHU#2 ON PLANS, SO |
| | DISCONNECT, LIGHT AND RECEPTACLE |
| | COMPLIANCE CAN BE DETERMINED. |
| | |
| | 8} UPSTAIR BATHS (NO NUMBER) MUST HAVE A |
| | GFI RECEPTACLE WITHIN 3' OF THE BASINS |
| | PER 210.52(D), 210.8(A)(1). |
| | |
| | 9} ALL ROOMS UPSTAIRS WITH TH EXCEPTION |
| | OF THE BATH ON THE SOUTH SIDE, ARE IN |
| | VIOLATION OF SPACING REQUIIREMENTS OF |
| | 210.52(A)(1)&(2). SEE REVIEWED PLAN. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |