Plan Review Notes
Plan Review Notes For Permit 05061880
Permit Number 05061880
Review Stop P
Sequence Number 3
Notes
Date Text
2006-03-25 00:00:00PAUL SCHMITZ
 [email protected]
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
 DENIED
 1)SHT. A5.01 REVISION DATED 03-01-06
  
 ?11-4.17 TOILET STALLS.
 EXCEPTION: NEW CONSTRUCTION
 (1) THE STANDARD ACCESSIBLE
 RESTROOM STALL SHALL CONTAIN AN
 ACCESSIBLE LAVATORY WITHIN IT, THE
 SIZE OF SUCH LAVATORY TO BE NOT
 LESS THAN 19 INCHES WIDE BY 17
 INCHES DEEP, NOMINAL SIZE, AND WALL
 MOUNTED.THE LAVATORY SHALL BE
 MOUNTED SO AS NOT TO OVERLAP THE
 CLEAR FLOOR SPACE AREAS REQUIRED
 BY ?11-4.17 (SEE FIGURE 11-30(A)
 AND FIGURE 11-30(E)) AND TO COMPLY
 WITH ?11-4.19 OF THE CODE.SUCH
 LAVATORIES SHALL BE COUNTED AS
 PART OF THE REQUIRED FIXTURE COUNT FOR
 THE BUILDING.
 (2) THE ACCESSIBLE WATER CLOSET
 SHALL BE LOCATED IN THE CORNER,
 DIAGONAL TO THE DOOR.
  
 END OF COMMENTS, QUESTIONS 561-805-6692