Plan Review Notes
Plan Review Notes For Permit 05061880
Permit Number 05061880
Review Stop E
Sequence Number 3
Notes
Date Text
2005-12-20 00:00:00****** UNSAT *****
  
 PLEASE SEE MINOR CHANGES NOTED ON
 REVISION COVER SHEET, HOWEVER THERE AHVE
 BEEN SOME MAJOR CHNAGES NOT ON ORIGINAL
 PLANS.
  
  
 1)NOTE: PLEASE SEE MANY WINDOWS ADDED
 NOT ON PREVIOUS ELECTRICAL PLANS.
 PLEASE SEE 210.62, 220.12A FOR MIN "SHOW
 WINDOWS" NOW REQUIRED ABOVE ALL WINDOWS.
 PLEASE ALSO ADJUST ALL CIRCUITING FOR
 THESE AS THEY ARE REQUIRED TO BE ON
 SEPARATE CIRCUITS.
  
 2)NOTE: PLEASE SEE A PANEL "E" IS SHOWN
 ON ON MDP , HOWEVER NO PANEL "E"
 SCHEDULE WAS SUBMITTED. IS THIS "EM" ON
 PLANS?
 PLEASE CORRELATE.
  
 3)NOTE: PLEASE SEE MDP IS NOW SHOWN AS
 MLO ON SCHEDULE AND MCB ON RISER. PLEASE
 SEE 230.70,230.71 ETC, A MAIN CIRCUIT
 BREAKER WILL BE REQUIRED.
 PLEASE MAKE NESS CHANGES.
 PLEASE ALSO SEE MDP SEEMS TO INDICATE A
 "SPARE" 800A 3-P IN SPACE #7?? PLEASE
 VERIFY.
  
 4)NOTE: PLEASE KNOW, DUE TO THE SCOPE OF
 WORK BEING DONE AND THE REQUIREMENTS OF
 CHAPTER 34 OF THE FBC, ALL EXISTING AND
 NEW ELECTRICAL SHALL MEET CURRENT 2002
 NEC.
 PLEASE SEE ALL OCP SHOWN AS EXISITNG FOR
 EQUIPMENT, A/C 'S ETC. THESE SHOULD BE
 VERIFIED IN FEILD AND ADJUSTED IF OCP
 DOES NOT MEET MIN OR IS SIZED TOO HIGH
 FOR UNIT.
  
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWERS WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  