| Date |
Text |
| 2005-07-07 00:00:00 | ********** UNSAT ****** |
| | |
| | 1)NOTE: PLEASE SEE MISSING TITLE |
| | BLOCK/TITLE BLOCK INFORMATION AS |
| | REQUIRED UNDER FAC 61G1-16.004, |
| | 61G15-23.002, FS 471.025 |
| | PLEASE ALSO SEE SOME ARCH SHEETS ARE NOT |
| | SEALED BY ARCH. FS 481.221 |
| | |
| | |
| | 2)NOTE: PLEASE CORRLETATE PLANS WITH |
| | SCOPE OF WORK ON APPLICATION ETC. |
| | PLEASE SEE PLANS CALL FOR GENERATOR |
| | ROOM? IS THERE GOING TO BE A GEN |
| | INSTALLED IN THIS SCOPE OF WORK? IF SO, |
| | PLEASE INCLUDE ALL INFORMATION AS |
| | REQUIRED. |
| | |
| | 3)NOTE: PLEASE CORRELATE RISER DIAGRAM |
| | WITH PANEL SCHEDULES SUBMITTED. |
| | PANEL A/C-2? |
| | 215.5 |
| | |
| | 4)NOTE: PLEASE SEE OCP FOR CU'S, PLEASE |
| | VERIFY SIZING. SEEMS EXCEED 150% OF FLA. |
| | ? |
| | 215.5 |
| | |
| | 5)NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| | AND PLEASE SHOW ALL CONTINUOUS LOADS AT |
| | 125%. 220.10,220.11,220.13 , |
| | 215.3,230.42 ETC. |
| | |
| | 6)NOTE: PLEASE SEE 2002 NEC 210.8B3 |
| | WHICH REQUIRES ALL 15- AND 20-AMPERE, |
| | 125-VOLT RECEPTACLES IN NONDWELLING-TYPE |
| | KITCHENS TO BE GFCI PROTECTED. THIS |
| | REQUIREMENT APPLIES TO EACH AND EVERY |
| | 15- AND 20-AMPERE, 125-VOLT KITCHEN |
| | RECEPTACLE, WHETHER OR NOT THE |
| | RECEPTACLE SERVES COUNTERTOP APPLIANCES. |
| | |
| | 7)NOTE: PLEASE INCLUDE ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH SUBMITTED PANEL |
| | SCHEDULES. |
| | PLEASE SEE 700.12E FOR CIRCUITING OF EM/ |
| | EXT LTS.THE BRANCH CIRCUIT FEEDING THE |
| | UNIT EQUIPMENT SHALL BE THE SAME BRANCH |
| | CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD |
| | OF ANY LOCAL SWITCHES. |
| | |
| | 8)NOTE: PLEASE CORRELATE PLANS WITH |
| | PANELS AND RISER DIAGRAM. PLEASE SHOW |
| | ALL PANELS ON PLANS. |
| | PLEASE SEE 110.26,408.7 ETC |
| | |
| | PLEASE SEE OTHER POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE BE SURE TO REMOVE ALL OLD/VOIDED |
| | SHEETS SND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STMAPING. ONE SET OF OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANYQUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |