| 2005-08-07 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05061880 |
| | ADD: 5400 S DIXIE HWY |
| | CONT: CONSILIUM ATLANTIC |
| | TEL: (954)788-3884 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 3) PLANS, SPECIFICATIONS,REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | THERE ARE PAGES MISSING THE RAISED SEAL, |
| | AND PAGES MISSING BOTH THE SEAL & |
| | SIGNATURE. |
| | |
| | 4) ACCESSIBLE DRESSING ROOM ISMISSING |
| | BENCH:11-4.35.4 BENCH. EVERY ACCESSIBLE |
| | DRESSING ROOM SHALL HAVE A 24 IN. BY |
| | 48 IN.(610 MM BY 1220 MM) BENCH FIXED |
| | TO THE WALL ALONG THE LONGER |
| | DIMENSION.THE BENCH SHALL BE MOUNTED |
| | 17 IN. TO 19 IN.(430 MM TO 485 MM) |
| | ABOVE THE FINISH FLOOR.CLEAR FLOOR |
| | SPACE SHALL BE PROVIDED ALONGSIDE THE |
| | BENCH TO ALLOW A PERSON USING A |
| | WHEELCHAIR TO MAKE A PARALLEL TRANSFER |
| | ONTO THE BENCH.THE STRUCTURAL STRENGTH |
| | OF THE BENCH AND ATTACHMENTS SHALL |
| | COMPLY WITH ?11-4.26.3.WHERE INSTALLED |
| | IN CONJUNCTION WITH SHOWERS, SWIMMING |
| | POOLS, OR OTHER WET LOCATIONS, WATER |
| | SHALL NOT ACCUMULATE UPON THE SURFACE OF |
| | THE BENCH AND THE BENCH SHALL HAVE A |
| | SLIP-RESISTANT SURFACE. |
| | |
| | 5) PLANS INDICATE THE USE OF POWER |
| | ACTIVATED AUTOMATIC SLIDING GLASS DOORS, |
| | PROVIDE COMPLIANCE WITH : |
| | 1012.4 HORIZONTAL SLIDING DOORS. |
| | APPROVED AND LISTED HORIZONTAL SLIDING |
| | DOORS COMPLYING WITH THE FOLLOWING |
| | CONDITIONS MAY BE USED IN A MEANS OF |
| | EGRESS WHEN SPECIFICALLY PERMITTED BY |
| | 1012.1.2, EXCEPTION 3. |
| | FOR A BIPARTING SLIDING DOOR IN THE |
| | EMERGENCY BREAK-OUT MODE, A DOOR LEAF |
| | LOCATED WITHIN A MULTIPLE-LEAF OPENING |
| | SHALL BE EXEMPT FROM THE MINIMUM 32 IN. |
| | (81-CM) SINGLE-LEAF REQUIREMENT OF IF A |
| | MINIMUM OF 32 IN.(81 CM) CLEAR OPENING |
| | IS PROVIDED BY ALL LEAFS BROKEN OUT. |
| | |
| | 6) RESTROOMS: 1204.2 SURROUNDING |
| | MATERIALS. THE WALLS AND FLOORS OF ALL |
| | PUBLIC REST ROOMS SHALL BE LINED WITH |
| | NONABSORBENT MATERIAL TO A HEIGHT OF 4 |
| | FT (1219 MM) ABOVE THE FLOOR. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |
| | |
| | |
| | |