| Date |
Text |
| 2005-08-29 00:00:00 | DENIED |
| | |
| | |
| | 3.FBC 1012.1.1 EGRESS DOORS USED AS AN |
| | EXIT DOOR SHALL PROVIDE A CLEAR |
| | OPENING OF NOT LESS THAN THE WIDTHS |
| | SHOWN IN TABLE 1004.THE MAXIMUM |
| | LEAF WIDTH OF THE DOOR SHALL NOT EXCEED |
| | 48 INCHES (1219 MM).EGRESS DOORS USED |
| | IN THE EXIT ACCESS SHALL PROVIDE A CLEAR |
| | OPENING OF NOT LESS THAN 32 INCHES (813 |
| | MM) WIDE.32" DOOR DOES NOT PROVIDE 32" |
| | CLEAR OPENING. |
| | |
| | 5. SUBMIT PRODUCT APPROVALS FOR THE |
| | FOLLOWING:STRAPS AND TIE-DOWNS. |
| | |
| | THE FOLLOWING IS REQUIRED FOR ALL |
| | PRODUCT APPROVALS SUBMITTED. |
| | ALL PRODUCT APPROVALS SUBMITTED WITH |
| | QUALITY ASSURANCE SHALL HACE THE |
| | FOLLOWING STATE PRODUCE APPROVAL |
| | ATTACHED. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 7.IF STAIR CASE IS OPEN IT SHALL |
| | COMPLY WITH FBC1006.2.4 |
| | EXTERIOR STAIRS SHALL BE SEPARATED FROM |
| | THE INTERIOR OF THE BUILDING BY WALLS |
| | WITH A FIRE RESISTANCE RATING OF NOT |
| | LESS THAN 1 HOUR, WITH FIXED OR |
| | SELF-CLOSING OPENING PROTECTIVES AS |
| | REQUIRED FOR ENCLOSED STAIRS.THIS |
| | PROTECTION SHALL EXTEND VERTICALLY FROM |
| | THE GROUND TO A POINT 10 FT (3048 MM) |
| | ABOVE THE TOPMOST LANDING OR THE ROOF |
| | LINE, WHICHEVER IS LOWER, AND |
| | HORIZONTALLY 10 FT (3048 MM) FROM EACH |
| | SIDE OF THE STAIRWAY.OPENINGS WITHIN |
| | THE 10 FT (3048 MM) HORIZONTAL EXTENSION |
| | OF THE PROTECTED WALLS BEYOND THE |
| | STAIRWAY SHALL BE EQUIPPED WITH FIXED |
| | 3/4 HOUR ASSEMBLIES. |
| | SEE A-03 OF 9 DOES NOT MATCH A-07 WEST |
| | ELEVATION PLEASE CLARIFY. |
| | SUBMIT SPECIFICATIONS AND PRODUCT |
| | APPROVALS FOR FIRE RATED WINDOWS USED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | |
| | ART LANGE |
| | BUILDING PLANS EXAMINER |
| | 805-6672 |
| | |
| | |