Plan Review Notes
Plan Review Notes For Permit 05061836
Permit Number 05061836
Review Stop B
Sequence Number 1
Notes
Date Text
2005-08-02 00:00:00DENIED
  
 1. 713.13(2) F.S.THE NOTICE OF
 COMMENCEMENT MUST BE RE-RECORDED BECAUSE
 THE DESCRIBED IMPROVEMENT OR
 CONSTRUCTION DID NOT COMMENCE WITHIN 90
 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.FBC 1012.1.1 EGRESS DOORS USED AS AN
 EXIT DOOR SHALL PROVIDE A CLEAR
 OPENING OF NOT LESS THAN THE WIDTHS
 SHOWN IN TABLE 1004.THE MAXIMUM
 LEAF WIDTH OF THE DOOR SHALL NOT EXCEED
 48 INCHES (1219 MM).EGRESS DOORS USED
 IN THE EXIT ACCESS SHALL PROVIDE A CLEAR
 OPENING OF NOT LESS THAN 32 INCHES (813
 MM) WIDE.
  
 4.FBC1005.4.1 EVERY SLEEPING ROOM
 LOCATED ON THE FIRST, SECOND AND THIRD
 STORY OR WITHIN BASEMENTS OF GROUP R
 OCCUPANCIES SHALL HAVE AT LEAST ONE
 EXTERIOR EMERGENCY ESCAPE AND RESCUE
 OPENING.THE EMERGENCY ESCAPE AND
 RESCUE OPENING SHALL BE PERMITTED TO
 OPEN INTO A SCREEN ENCLOSURE, OPEN
 TO THE ATMOSPHERE, WHERE A SCREEN DOOR
 IS PROVIDED LEADING AWAY FROM THE
 RESIDENCE.SHOW HOW WINDOWS WILL COMPLY
 WITH THIS SECTION.
  
 5. SUBMIT PRODUCT APPROVALS FOR THE
 FOLLOWING:POLY STICK UNDERLAYMENT,
 ALTUSA TILE AND STRAPS AND TIE-DOWNS.
 ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HACE THE
 FOLLOWING STATE PRODUCE APPROVAL
 ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6.SHOW PROPOSED ELEVATIONS FOR A-07.
  
 7.ARE STAIRWAYS ENCLOSED NOW?IF SO
 SHOW ON PLANS.THERE IS A DOOR SHOWN ON
 THE BOTTOM OF THE STAIR CASE?
 IF STAIR CASE IS OPEN IT SHALL COMPLY
 WITH FBC1006.2.4
 EXTERIOR STAIRS SHALL BE SEPARATED FROM
 THE INTERIOR OF THE BUILDING BY WALLS
 WITH A FIRE RESISTANCE RATING OF NOT
 LESS THAN 1 HOUR, WITH FIXED OR
 SELF-CLOSING OPENING PROTECTIVES AS
 REQUIRED FOR ENCLOSED STAIRS.THIS
 PROTECTION SHALL EXTEND VERTICALLY FROM
 THE GROUND TO A POINT 10 FT (3048 MM)
 ABOVE THE TOPMOST LANDING OR THE ROOF
 LINE, WHICHEVER IS LOWER, AND
 HORIZONTALLY 10 FT (3048 MM) FROM EACH
 SIDE OF THE STAIRWAY.OPENINGS WITHIN
 THE 10 FT (3048 MM) HORIZONTAL EXTENSION
 OF THE PROTECTED WALLS BEYOND THE
 STAIRWAY SHALL BE EQUIPPED WITH FIXED
 3/4 HOUR ASSEMBLIES.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  