| Plan Review Notes For Permit 05061832 |
| Permit Number |
05061832 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-21 00:00:00 | BUILDING REVIEW CHECKLIST: | | | | | | 1- PROVIDE DESIGN PRESSURES ACCORDING TO | | | THE BUILDING GEOMETRICAL SHAPE, HEIGHT, | | | OPEN OR ENCLOSED BUILDING, EXPOSURE | | | CATEGORY, TRIBUTARY AREA AND ZONE | | | LOCATION AS REQUIRED BY ASCE 7-98. | | | PROVIDE ENGINEERED CALCULATIONS. SECTION | | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | | | | 2- ENGINEERED WIND LOAD TABLE NEEDS TO | | | BE SIGNED AND SEALED BY THE ENGINEER WHO | | | PREPARED IT AS REQUIRED BY CHAPTER 471 | | | FLORIDA STATUTES. | | | TABLE IS GENERIC. ENGINEER TO PROVIDE | | | CALCULATIONS FOR ACTUAL BUILDING | | | CONSIDERING THE FACTS LISTED ON ITEM #1 | | | ABOVE. SEC. 104.2.1.2 CITY AMENDMENTS TO | | | FBC 2001. | | | | | | 3- PROVIDE COMPLETE INFORMATION ON SHEET | | | 17 AS REQUIRED BY GUIDE TO USE CHARTS | | | AND GRAPHS ON SHEET 2 OF THE ROLL UP | | | SHUTTER DRAWINGS. | | | | | | 4- NEED RECORDED NOTICE OF COMMENCEMENT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ AT (561)805-6712. |
|