Plan Review Notes
Plan Review Notes For Permit 05061829
Permit Number 05061829
Review Stop M
Sequence Number 1
Notes
Date Text
2007-08-14 09:32:49PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER
 1 CITY OF WEST PALM BEACH AMENDMENTS.
  
 *** DENIED ***
 1) PLANS ON FILE ARE SEALED BY AN ARCHITECT (ALBERT A.
 GARGIULO) SO ONLY HE CAN MAKE REVISION TO HIS PLANS.
  
 2) SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC
 13-101.2.1.
  
 3) SUBMIT COOLING LOAD CALCULATIONS, SEE 2004 FBC
 13-607.1.ABC.1.
  
 4) STATE WHAT H/S RXBH24A10J STANDS FOR.
  
 5) SHOW SEER OF A/C SYSTEM ON PLAN, SEE 2004 FBC
 13-607.1.ABC.3.2.1.
  
 6) SHOW HEATER SIZE ON PLAN.
  
 7) ELECTRICAL PLAN ON FILE SHOWS EXHAUST FANS IN ALL
 BATHROOMS, IF SO SHOW ON MECHANICAL PLAN IF NOT REVISE
 ELECTRICAL PLAN, SEE 2004 FBC/R R303.3 EXCEPT.
  
 8) SHOW CFM'S AT ALL BATHROOM EXHAUST FANS, SEE 2004
 FBC?R R303.3 EXCEPT.
  
 9) MECHANICAL PLAN SUBMITTED SHOWS A/C IN UNIT AR ONLY,
 THIS WILL REQUIRE A REVISION AND MORE FEES IF A/C IS TO
 BE INSTALLED IN UNIT A ALSO.
  
 10) PLEASE ADJUST THE VALUE ON THE BUILDING PERMIT TO
 INCLUDE THE A/C AND PAY THE ADDITIONAL FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].