| Plan Review Notes For Permit 05061829 |
| Permit Number |
05061829 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-08-14 09:32:49 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER | | | 1 CITY OF WEST PALM BEACH AMENDMENTS. | | | | | | *** DENIED *** | | | 1) PLANS ON FILE ARE SEALED BY AN ARCHITECT (ALBERT A. | | | GARGIULO) SO ONLY HE CAN MAKE REVISION TO HIS PLANS. | | | | | | 2) SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC | | | 13-101.2.1. | | | | | | 3) SUBMIT COOLING LOAD CALCULATIONS, SEE 2004 FBC | | | 13-607.1.ABC.1. | | | | | | 4) STATE WHAT H/S RXBH24A10J STANDS FOR. | | | | | | 5) SHOW SEER OF A/C SYSTEM ON PLAN, SEE 2004 FBC | | | 13-607.1.ABC.3.2.1. | | | | | | 6) SHOW HEATER SIZE ON PLAN. | | | | | | 7) ELECTRICAL PLAN ON FILE SHOWS EXHAUST FANS IN ALL | | | BATHROOMS, IF SO SHOW ON MECHANICAL PLAN IF NOT REVISE | | | ELECTRICAL PLAN, SEE 2004 FBC/R R303.3 EXCEPT. | | | | | | 8) SHOW CFM'S AT ALL BATHROOM EXHAUST FANS, SEE 2004 | | | FBC?R R303.3 EXCEPT. | | | | | | 9) MECHANICAL PLAN SUBMITTED SHOWS A/C IN UNIT AR ONLY, | | | THIS WILL REQUIRE A REVISION AND MORE FEES IF A/C IS TO | | | BE INSTALLED IN UNIT A ALSO. | | | | | | 10) PLEASE ADJUST THE VALUE ON THE BUILDING PERMIT TO | | | INCLUDE THE A/C AND PAY THE ADDITIONAL FEE. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL: [email protected]. |
|