| Plan Review Notes For Permit 05061829 |
| Permit Number |
05061829 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-21 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE INDICATE THE CONDUCTOR AND | | | CONDUIT SIZE FROM THE DISCONNECT TO THE | | | PANEL, ON THE RISER. ALSO NOTE AN | | | EQUIPMENT GROUND PER 250.122 IS REQUIRED | | | PAST THE FIRST MEANS OF DISCONNECT. | | | | | | 2} THE SMALL APPLIANCE CIRCUITS MUST BE | | | CALCULATED AT 1500VA PER 210.11(C)(1). | | | | | | 3} THE GEC MUST BE RAN TO FOOTER STEEL | | | PER 2580.50. | | | | | | 4} SMOKE DETECTORS ARE REQUIRED ON THE | | | FIRST FLOOR IN CLOSE PROXIMETY TO THE | | | STAIRWELL PER 905.2.2 FBC. | | | | | | 5} THE MASTER BEDROOM AND BEDROOM #3 | | | NEED RECEPTACLES ADDED TO COMPLY WITH | | | 210.52((A)(1&2) SPACING REQUIREMENTS. | | | | | | 6} THE MASTER BATHROOM NEEDS A | | | RECEPTACLE ADDED TO COMPLY WITH | | | 210.52(D). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|