Plan Review Notes
Plan Review Notes For Permit 05061829
Permit Number 05061829
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-21 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE INDICATE THE CONDUCTOR AND
 CONDUIT SIZE FROM THE DISCONNECT TO THE
 PANEL, ON THE RISER. ALSO NOTE AN
 EQUIPMENT GROUND PER 250.122 IS REQUIRED
 PAST THE FIRST MEANS OF DISCONNECT.
  
 2} THE SMALL APPLIANCE CIRCUITS MUST BE
 CALCULATED AT 1500VA PER 210.11(C)(1).
  
 3} THE GEC MUST BE RAN TO FOOTER STEEL
 PER 2580.50.
  
 4} SMOKE DETECTORS ARE REQUIRED ON THE
 FIRST FLOOR IN CLOSE PROXIMETY TO THE
 STAIRWELL PER 905.2.2 FBC.
  
 5} THE MASTER BEDROOM AND BEDROOM #3
 NEED RECEPTACLES ADDED TO COMPLY WITH
 210.52((A)(1&2) SPACING REQUIREMENTS.
  
 6} THE MASTER BATHROOM NEEDS A
 RECEPTACLE ADDED TO COMPLY WITH
 210.52(D).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  