| Plan Review Notes For Permit 05061816 |
| Permit Number |
05061816 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-20 00:00:00 | DENIED; | | | 1.PIPING SCHEMATIC SHOWS CLEAN LINE | | | PLUMBING PLAN DOES NOT PLEASE CORRECT. | | | 2.PLEASE ADD TO NOTES; | | | A.PUMPS AND EQUIPMENT SHALL BE | | | MOUNTED ON A SUBSTANTIAL BASE IN A | | | MANNER THAT WILL ELIMINATE STRAIN ON | | | PIPING. SLAB SHALL BE A NOMINAL 4" | | | THICK. | | | B.VALVES SHALL BE OF AN APPROVED TYPE | | | PER FBC 2001 PLUMBING MUST BE READILY | | | ACCESSIBLE FOR MAINT. FULL WAY VALVES | | | SHALL BE INSTALLED. WHERE CHECK VALVES | | | ARE INSTALLED THEY SHALL BE OF THE SWING | | | OR VERTICAL CHECK PATTERNS. | | | C.ALL WATER HEATER EQUIPMENT SHALL BE | | | INSTALLED WITH FLANGES OR UNIONS | | | CONNECTIONS ADJACENT TO THE HEATER. | | | D.GAS PIPING SHALL COMPLY WITH FBC FUIL | | | GAS. SEPARATE PLANS AND PERMIT REQUIRED. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|