| 2005-07-18 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE SUBMIT DETAILS FOR THE PANEL | | | SHOWN ON THE SCHEMATIC, FEEDER AND | | | CONDUIT SIZE AND TYPE, PANEL RATING AND | | | OCP, PANEL SCHEDULE AND COMPUTED LOAD. | | | | | | 2} THERE IS A HEATER SHOWN IN THE | | | SCHEMATIC, AND LOAD CALCS SUBMITTED. THE | | | DATA SHEET SAYS NO HEATER AND NO HEATER | | | SPECS WERE SUBMITTED. PLEASE CLARIFY, | | | HEATER, NO HEATER AND SUBMIT/TAKE OUT, | | | THE PERTINENT DOCUMENTS. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|