2005-07-20 00:00:00DENIED;
 1.PIPING SCHEMATIC AND PLUMBING PLAN DO
 NOT MATCH. SCHEMATIC SHOWS 2 SETS OF OF
 MAIN DRAINS PLUMBING PLAN SHOWS 1 SET.
 PLEASE CORRECT.
 2.NOTE ON PLANS EQUIPMENT SLAB TO BE A
 MINIMUM OF 4" THICK.
 3.VALVES SHALL BE APPROVED AND READILY
 ACCESSIBLE FOR MAINT. OR REMOVAL. FULL
 FLOW VALVES TO BE USED. IF CHECK VALVES
 ARE INSTALLED THEY SHALL BE SWING OR
 VERTICAL CHECK VALVES.
 4.ALL WATER HEATERS SHALL BE INSTALLED
 WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695