Plan Review Notes
Plan Review Notes For Permit 05061773
Permit Number 05061773
Review Stop P
Sequence Number 1
Notes
Date Text
2005-08-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS:
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
 2. SHTS AE-6 & AE-7 INDICATE THAT THE
 LADIES ROOMS SHALL BE ELIMINATED OR
 DELETED. PLEASE SUBMIT CALCULATIONS FOR
 MINIMUM FACILITIES PER TABLE 1003.1
 BUILDING, AND 403.1 PLUMBING. INDICATE
 THE NUMBER OF WATER CLOSETS, URINALS,
 LAVS. ECT. SHOW THE LOCATION OF THE
 REQUIRED SERVICE SINK AND DRINKING
 FOUNTAINS.
 3. SHTS AE-6 & AE-7 IN THE REMOVAL OF
 ANY PARY OF A DRAINAGE SYSTEM, DEAD ENDS
 SHALL BE PROHIBITED. SECTION 704.5. -
 FIELD INSPECTOR SHALL INSPECT CAPPED OFF
 LINES PRIOR TO COVERING.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]