Plan Review Notes
Plan Review Notes For Permit 05061773
Permit Number 05061773
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-07-27 00:00:00******DENIED******
  
 1) PLEASE SEE OTHER REVIEW COMMENTS IN
 REGARDS TO FS AND FAC REQUIREMENTS FOR
 ALL SHEETS.
  
 2) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 3) AS STATED ON DRAWINGS, APPROPRIATE
 EXIT HARDWARE SHALL INCLUDE PANIC
 HARDWARE SERVING ASSEMBLY AREAS IN
 EXCESS OF 100 PERSONS.
  
 4) IT IS UNDERSTOOD THAT THIS BUILDING
 IS EXISTING. PLEASE SHOW ADDRESS ON
 BUILDING THAT SHALL BE AT LEAST 6" IN
 HEIGHT AND CONTRASTING TO THE
 BACKGROUND.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 805-6722 OR 804-4756