Plan Review Notes
Plan Review Notes For Permit 05061773
Permit Number 05061773
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-07 00:00:00********** UNSAT *********
  
 1)NOTE: PLEASE SEE MISSING TITLE BLOCK
 AND TITLE BLOCK INFORMATION AS REQUIRED
 UNDER FAC 61G1-16.004,61G15-23.002 FS
 481.219, 471.023
 PLEASE SEE THIS IS REQUIRED ON ALL
 SHEETS AND FOR ALL TRADES WHEATHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 2)NOTE: PLEASE INDICATE CIRCUITING ON
 PLANS. IF NEW , PLEASE IDENTIFY CIRCUIT
 #'S AND TO WHICH PANEL(S) THEY ARE FED.
 IF EXISTING, PLEASE INDICATE.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  