| Plan Review Notes For Permit 05061769 |
| Permit Number |
05061769 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-03-16 00:00:00 | ********** UNSAT ************ | | | | | | 1)NOTE: PLEASE SEE THERE IS NOT ENOUGH | | | INFORMATION FOR REVIEW FOR ELECTRICAL. | | | PLEASE REVISE AND COMPLETE ELECTRICAL | | | REVISIONS TO WHAT NOW APPEARS TO BE AN | | | ADDITION. | | | 215.5 | | | | | | 2)NOTE: PLEASE SEE BUILDING REVIEW | | | COMMENTS ALSO WITH RESPECT TO VALUATION | | | OF PROJECT TO BE INCREASED FOR NEW WORK. | | | FBC 104.6.5/108.3 | | | | | | 3)NOTE: PLEASE SEE NOTES BELOW AS THESE | | | ITEMS WERE REDLINED ON PREVIOUS PLANS | | | AND NEED TO BE UPDATED AND CORRECTED | | | WHEN SUBMITTING NEW REVISED ELECTRICAL | | | PLANS. | | | | | | ************************************** | | | *** NOTED*** | | | | | | ALL ELECTRICAL SERVICE SHOWN IS EXSITNG, | | | INCLUDING GENERATOR. | | | REDLINED CONSTRICTION SPEC BOOKS, AS | | | GENERATOR IS MENTIONED. | | | | | | REDLINED NFPA-72, TO BE 2002, 1999 | | | REFERENCED. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|