| 2006-02-27 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05061769 |
| | ADD: 2090 N CONGRESS AVE |
| | CONT: DOOLEY MACK CONST. |
| | TEL: (561)635-6935 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVISION: |
| | ACTION: DENIED |
| | |
| | 1) PLANS NEED TO INDICATE TO WHICH CODE |
| | THEY ARE DESIGNED TOO. IT APPEARS THIS |
| | IS AN ADDITION TO THE ORIGINAL BUILDING. |
| | IF THIS IS A REVISION TO THE ORIGINAL |
| | PERMIT PLEASE UP THE VALUE OF THE |
| | PROJECT. |
| | |
| | 2) 2001 FL. BLD CODE 1606.1.4 THE |
| | FOLLOWING INFORMATION RELATED TO WIND |
| | SHALL BE SHOWN ON THE CONSTRUCTION |
| | DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 3) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) EXTERIOR DOOR |
| | B) EFIS SYSTEM/ DENSEGLASS |
| | C) EXTERIOR LOUVER |
| | D) ROOFING ASSEMBLIES |
| | |
| | 4) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 5) NOTE ONPLAN INDICATES WORK TO BE |
| | COMPLETED AT N 130, IS THIS A NEW |
| | EXTERIOR MECHANICAL CLOSET OR A INTERIOR |
| | |
| | CLOSET? |
| | |
| | 6) PROVIDE THE MINIMUM BLDG TYPE PER |
| | TABLE 500. |
| | |
| | 7)1403.1.6 IN ORDER TO PROVIDE FOR |
| | INSPECTION FOR TERMITE INFESTATION, |
| | CLEARANCE BETWEEN EXTERIOR WALL |
| | COVERINGS AND FINAL EARTH GRADE ON THE |
| | EXTERIOR OF A BUILDING SHALL NOT BE |
| | LESS THAN 6 INCHES (152 MM). |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |