| Plan Review Notes For Permit 05061769 |
| Permit Number |
05061769 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-11-15 00:00:00 | DENIED: | | | 1.IN ACCORDANCE WITH FAC 61G15-23.002 | | | (2), ENGINEER SHALL HAVE PRINTED NAME & | | | LICENSE NUMBER INDICATED ON THE TITLE | | | BLOCK. | | | | | | 2.PLAN SHEET M-1; AHU-N102 INDICATES | | | THE NEW CONDENSATE TERMINATING INTO A | | | HUB DRAIN.PER THE CITY CODE SEC. | | | 90-125 (B)(5), THE CONDENSATE SHALL NOT | | | TERMINATE INTO THE SANITARY DRAIN. | | | PLEASE CLARIFY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|