Plan Review Notes For Permit 05061769
Permit Number 05061769
Review Stop M
Sequence Number 1
Notes
Date Text
2005-07-28 00:00:00PLAN DENIED
 .1) PLEASE REFER TO SECTION 7.1.3.2.1
 NFPA 101 PENETRATION IN STAIR WELLS.
 2) NEED FIRE DAMPER IN ROOM N103.
 3) PLEASE SUBMIT EQUIPMENT MODEL NUMBER
 AND SEER ON PLAN
 4) PLEASE SUBMIT FRESH AIR CALCULATIONS
 ON PLAN.
 5) PLEASE SUBMIT ENERGY CALCULATIONS
 PLAN REVIEW BY HAROLD MOSER 651-805-6732