2005-07-13 00:00:00******DENIED******
  
 1) FIGURE A-4 ILLUSTRATES A PROPOSED
 REMOVAL PLAN. IT IS PRESUMED THAT THIS
 REFERENCES THE SECOND FLOOR. PLEASE SHOW
 THIS ON THE DRAWING.
  
 2) ALL CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
 3) THE SPEC MANUAL REFERENCES A FIRE
 WATCH. A REQUIRED FIRE WATCH MUST BE
 APPROVED BY THE CITY FIRE MARSHAL. THE
 APPROVED FIRE WATCH SHALL BE IN
 ACCORDANCE WITH LOCAL REQUIREMENTS AND A
 WRITTEN POLICY WILL BE AVAILABLE TO
 ASSIST WITH THE PROCESS.
  
 4) THE DRAWINGS DON'T SHOW ANY ENCLOSURE
 RATING FOR ELEVATOR #2 AND ASSOCIATED
 EQUIPMENT ROOM. PLEASE SHOW ALL EXISTING
 VERTICAL ENCLOSURE RATINGS.
  
 5) NEW DUCT SMOKE DETECTORS WHERE
 PROVIDED MUST BE WIRED TO THE FIRE ALARM
 SYSTEM TO INITIATE A GENERAL FIRE ALARM
 IN ADDITION TO FAN SHUT DOWN.
  
 6) PLEASE SHOW THE LOCATIONS OF NEW AND
 OR EXISTING ILLUMINATED EXIT SIGNS AND
 EMERGENCY LIGHTING FACILITIES.
  
 7) WILL THIS WORK IMPACT EXISTING
 BUILDING LIFE SAFETY EQUIPMENT?
  
 8) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR THE FIRE SPRINKLER AND
 FIRE ALARM REMODEL.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 805-6722 OR 835-2951