| 2005-07-13 00:00:00 | ******DENIED****** |
| | |
| | 1) FIGURE A-4 ILLUSTRATES A PROPOSED |
| | REMOVAL PLAN. IT IS PRESUMED THAT THIS |
| | REFERENCES THE SECOND FLOOR. PLEASE SHOW |
| | THIS ON THE DRAWING. |
| | |
| | 2) ALL CONSTRUCTION, ALTERATION AND |
| | DEMOLITION SHALL COMPLY WITH NFPA 241. |
| | |
| | 3) THE SPEC MANUAL REFERENCES A FIRE |
| | WATCH. A REQUIRED FIRE WATCH MUST BE |
| | APPROVED BY THE CITY FIRE MARSHAL. THE |
| | APPROVED FIRE WATCH SHALL BE IN |
| | ACCORDANCE WITH LOCAL REQUIREMENTS AND A |
| | WRITTEN POLICY WILL BE AVAILABLE TO |
| | ASSIST WITH THE PROCESS. |
| | |
| | 4) THE DRAWINGS DON'T SHOW ANY ENCLOSURE |
| | RATING FOR ELEVATOR #2 AND ASSOCIATED |
| | EQUIPMENT ROOM. PLEASE SHOW ALL EXISTING |
| | VERTICAL ENCLOSURE RATINGS. |
| | |
| | 5) NEW DUCT SMOKE DETECTORS WHERE |
| | PROVIDED MUST BE WIRED TO THE FIRE ALARM |
| | SYSTEM TO INITIATE A GENERAL FIRE ALARM |
| | IN ADDITION TO FAN SHUT DOWN. |
| | |
| | 6) PLEASE SHOW THE LOCATIONS OF NEW AND |
| | OR EXISTING ILLUMINATED EXIT SIGNS AND |
| | EMERGENCY LIGHTING FACILITIES. |
| | |
| | 7) WILL THIS WORK IMPACT EXISTING |
| | BUILDING LIFE SAFETY EQUIPMENT? |
| | |
| | 8) SEPARATE SHOP DRAWINGS AND PERMITS |
| | ARE REQUIRED FOR THE FIRE SPRINKLER AND |
| | FIRE ALARM REMODEL. |
| | |
| | |
| | MIKE WENNERGREN, A/CAPTAIN |
| | WPBFR(561) 805-6722 OR 835-2951 |