Plan Review Notes
Plan Review Notes For Permit 05061769
Permit Number 05061769
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-11 00:00:00IN ELEC FOR REVIEW, NOTES TO FOLLOW.
 ********** UNSAT ************
  
 1)NOTE: PLEASE SEE IT IS UNCLEAR IF
 SERVICE SHOWN IS TO BE NEW OR EXSITING.
 RISER SEEMS TO INDICATE ALL NEW, HOWEVER
 THE FOUR PANEL SCHEDULES SUBMITTED
 INDICATE AS EXSITING?
 IF NEW, PLEASE SEE THE FOLLOWING.
  
 2)NOTE: PLEASE SEE MDP-2 SHOWN ON PLANS
 BUT NOT ON RISER?
 COULD NOT LOCATE WHAT IS SHOWN AS SECOND
 SERVICE "DP-6" ON PLANS FOR VERIFICATION
 OF GROUPING MAINS?
 230.76,230.79,230.72,215.5 ETC
  
 3)NOTE: PLEASE SEE MDP-2 DOES NOTE SEEM
 TO MEET 110.26
  
 4)NOTE: PLEASE SEE SPECBOOKSSUBMITTED
 SEEM TO INDICATE A NEW ATS, PANELS,
 GENERATOR ETC??
 IF NEW? PLEASE SUBMIT ALL MANUFACTURE
 SPECS/CUT SHEETS FOR ATS, GEN , FUEL
 TANKS ETC. PLEASE BE SURE ALL LISTINGS
 ARE INDICATED BY A NRTL.
 110.4, 90.7, 225.31-225.36
 PLEASE SEE RISER DIAGRAM IN UNCLEAR FOR
 FEEDS TO ATS SWITCHES? GUTTERS, TAPS?
 240.21 ETC?
 LOCATION OF GEN , ATS ETC TO BE SHOWN ON
 ALL PLANS, INCLUDING A SITE PLAN TO BE
 SUBMITTED, SEEE ZONING COMMENTS.
  
 5)NOTE: PLEASE SEE NO INFORMATION FOR
 MDP-1 WAS GIVEN TO VERIFY SEC'S? PLEASE
 ALSO SEE 250.66 FOR SIZING OF GROUNDING
 ELECTRODE CONDUCTOR.
 215.5
  
 6)NOTE: PLEASE SEE LIGHTNING PROTECTION
 SYSTEM IS INDICATED IN SPEC BOOK,
 HOWEVER NO PLANS SUBMITTED. IF SYSTEM IS
 TO BE PERMITTED UNDER THIS SCOPE OF
 WORK, PLEASE SUBMIT COMPLETE PLANS FOR
 PROPOSED SYSTEM.
  
 7)NOTE: PLEASE SEE PAGE 16470 OF SPEC
 BOOK WHICH REFERENCES A 2000 NFPA-70
 (NEC)> PLEASE SEE WE ARE UNDER THE 2002
 NEC WHICH WAS ADOPTED JULY 1ST, 2003.
 PLEASE ALSO SEECODES REFERENCED ON
 SOME LOCATION ON PLANS/IN NOTES ARE PER
 1999 NEC. , (384) NOTE #6 GEN NOTES.
  
 8)NOTE: PLEASE SEE "IF NEW", PLEASE
 SUBMIT COMPLETE LOAD CALCULATIONS BASED
 ON MIN AS SETFORTH IN 2002 NEC.
 PLEASE SHOW ALL CONTINOUS LOADS @ 125%
 215.3,230.42 ETC.
  
 9)NOTE: PLEASE SEE FAC 61G15-23.002 FOR
 ALL INFORMATION REQUIRED TO BE ON TITLE
 BLOCK. FS 471.023
 PLEASE ALSO VERIFY ENGINEERING FIRM OF
 RECORD? TWO SHOWN?
 PLEASE ALSO SEE MISSING TITLE BLOCK
 INFORMATION REQUIRED ON TRADE SHEETS FOR
 ARCHITECT/FIRM. FAC 61G1-16.004. PLEASE
 SEE ALL INFORMATION AS SHOWN ON A-SHEETS
 SHOULD ALSO BE SHOWN ON TRADE TITLE
 BLOCKS.
 PLEASE BE SURE ALL SEALS ARE CLEAR AND
 VISABLE WITH ALL INFORMATION AS SETFORTH
 UNDER FS 471.025,AND FS 481.221, PLEASE
 SEE SOME SEALS ARE NOT VER READABLE.
 PLEASE SEE THIS IS REQUIRED FOR ALL
 SHEETS AND FOR ALL TRADES WHEATHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S)>
  
 PLEASE BE SURE TO SEE ANY COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 ONE SET OF OLD SHEETS SHOULD BE
 SUBMITTED FOR REFERNCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  