| Date |
Text |
| 2005-08-07 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05061769 |
| | ADD: 2090 N CONGRESS |
| | CONT: DOOLEYMACK CONSTRUCTORS |
| | TEL: (941)809-7272 |
| | |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 2) FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | THE ELECTRICAL PLAN INDICATES PHASING OF |
| | THIS PROJECT, WILL THE PATENTS BE MOVED |
| | OUT OF THE WORK AREA DURING EACH PHASE? |
| | IN PHASE II THE COMMON AREAS WILL BE |
| | REMODELED,WHEREWILL THE TEMPORARY |
| | COMMON AREAS BE ? |
| | |
| | 3) PROVIDE A LIFE SAFETY PLAN FOR EACH |
| | PHASED WORK AREA. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |
| | |
| | |
| | |
| | |