2005-07-25 00:00:00NO MECHANICAL PLANS OR CONTRACTOR
 INDICATED WITH PERMIT APPLICATION,
 PLEASE NOTE THE FOLLOWING:
  
 1.PLAN SHEET A-2 DETAIL OF THE 3RD
 FLOOR OVERALL PLAN INDICATES CORRIDOR TO
 HAVE A 1 HR RATING.FIRE DAMPERS WILL
 BE REQUIRED IN THE DIFFUSERS PER 2001
 FBC(M)607.2.
  
 2.PLAN SHEET A-2 DETAIL OF THE
 EXISTING CLASSROOM INDICATES EXTENDING
 THE EXISTING DUCTWORK AND PROVIDING NEW
 GRILLE.PLEASE NOTE, SHOULD DUCTWORK
 PENETRATE THE 1 HR PARTITION A FIRE
 DAMPER WILL BE REQUIRED OR OR DUCT
 INSTALLATION SHALL COMPLY WITH 2001
 FBC(M)607.1.3 #3 ITEMS 1 THROUGH 4.
  
 3.PLEASE PROVIDE PLANS WITH MECHANICAL
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.