| Plan Review Notes For Permit 05061767 |
| Permit Number |
05061767 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-07-25 00:00:00 | NO MECHANICAL PLANS OR CONTRACTOR | | | INDICATED WITH PERMIT APPLICATION, | | | PLEASE NOTE THE FOLLOWING: | | | | | | 1.PLAN SHEET A-2 DETAIL OF THE 3RD | | | FLOOR OVERALL PLAN INDICATES CORRIDOR TO | | | HAVE A 1 HR RATING.FIRE DAMPERS WILL | | | BE REQUIRED IN THE DIFFUSERS PER 2001 | | | FBC(M)607.2. | | | | | | 2.PLAN SHEET A-2 DETAIL OF THE | | | EXISTING CLASSROOM INDICATES EXTENDING | | | THE EXISTING DUCTWORK AND PROVIDING NEW | | | GRILLE.PLEASE NOTE, SHOULD DUCTWORK | | | PENETRATE THE 1 HR PARTITION A FIRE | | | DAMPER WILL BE REQUIRED OR OR DUCT | | | INSTALLATION SHALL COMPLY WITH 2001 | | | FBC(M)607.1.3 #3 ITEMS 1 THROUGH 4. | | | | | | 3.PLEASE PROVIDE PLANS WITH MECHANICAL | | | PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|