2005-07-11 00:00:00DENIED
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) EXISTING WALLS APPEAR TO BE PART OF
 EGRESS ACCESS CORRIDORS, WHICH ARE
 REQUIRED TO HAVE A ONE HOUR FIRE RATING.
 SPECIFY FIRE RATING OF WALLS ON THE
 PLAN. SEE FBC 704.2.4.
  
 3) IF THE WALL ON THE FIRST FLOOR IS
 REQUIRED TO HAVE A ONE HOUR FIRE RATING
 SPECIFY THAT THE NEW DOOR HAS A FIRE
 PROTECTION RATING OF 20 MIN. AS REQUIRED
 BY FBC 705.1.3.2.2.
  
 4) THE WALLS ON THE THIRD FLOOR ARE
 REQUIRED TO EXTEND TO THE ROOF DECK OR
 FLOOR ABOVE, UNLESS THE CEILING IS PART
 OF AN ASSEMBLY WITH A FIRE RATING AT
 LEAST EQUAL TO THE WALL. SEE FBC
 704.2.1.3.
  