| Plan Review Notes For Permit 05061767 |
| Permit Number |
05061767 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-11 00:00:00 | DENIED | | | 1)A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) EXISTING WALLS APPEAR TO BE PART OF | | | EGRESS ACCESS CORRIDORS, WHICH ARE | | | REQUIRED TO HAVE A ONE HOUR FIRE RATING. | | | SPECIFY FIRE RATING OF WALLS ON THE | | | PLAN. SEE FBC 704.2.4. | | | | | | 3) IF THE WALL ON THE FIRST FLOOR IS | | | REQUIRED TO HAVE A ONE HOUR FIRE RATING | | | SPECIFY THAT THE NEW DOOR HAS A FIRE | | | PROTECTION RATING OF 20 MIN. AS REQUIRED | | | BY FBC 705.1.3.2.2. | | | | | | 4) THE WALLS ON THE THIRD FLOOR ARE | | | REQUIRED TO EXTEND TO THE ROOF DECK OR | | | FLOOR ABOVE, UNLESS THE CEILING IS PART | | | OF AN ASSEMBLY WITH A FIRE RATING AT | | | LEAST EQUAL TO THE WALL. SEE FBC | | | 704.2.1.3. | | | | | | IF YOU HAVE QUESTIONS CALL: | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|