Notes
Date Text
2005-07-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA STATUTES
 FBC-2001 CHAPTER 1
  
 1. PLANS ARE REQUIRED, AND SHALL BE
 DESIGNED BY AN ARCHITECT PER FS
 481.229(1)(C).
 2. A SANITARY RISER DIAGRAM IS REQUIRED
 PER SECTION 104.3.1.1. SHOW ALL PIPE
 SIZES, VENTING, AND POINT OF CONNECTION.
 3. A WATER RISER DIAGRAM IS REQUIRED PER
 SECTION 104.3.1.1. SHOW ALL PIPE SIZES,
 VALVES, POINT OF CONNECTION, AND WATER
 HAMMER ARRESTORS IF REQUIRED BY SECTION
 604.9 OF THE PLUMBING CODE. (QUICK
 CLOSING VALVES IE: ICE MAKER, DISH
 WASHER, OR WASH MACHINE IN INSTALLED).
  