| Plan Review Notes For Permit 05061756 |
| Permit Number |
05061756 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-04 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | | | | 1. SHT A-1 BATHROOM FOR THE MEZZANINE | | | SHALL BE ACCESSIBLE PER SECTION | | | 11-4.1.3(11). - SUBMIT A DETAIL FOR THE | | | BATHROOM SHOWING COMPLIANCE WITH | | | SECTIONS 11-4.16, 11-4.19, 11-4.21, | | | 11-4.22 AND ALL SUBSECTIONS. | | | 2. SUBMIT A SANITARY RISER ISOMETRIC | | | SHOWING ALL PIPE SIZES, TRAPS, VENTS AND | | | POINTS OF CONNECTION AND TERMINATION. | | | SECTION 104.3.1.1. | | | 3. SUBMIT A WATER RISER ISOMETRIC | | | DIAGRAM SHOWING ALL PIPE SIZES, VALVES | | | ECT. SHOW POINT OF CONNECTION. SECTION | | | 104.3.1.1. | | | 4. AN RPZ BACKFLOW IS REQUIRED ON THE | | | WATER SERVICE OF THE BUILDING. SECTION | | | 608.13.2. | | | 5. PER TABLE 403.1 A DRINKING FOUNTAIN | | | AND A SERVICE SINK ARE REQUIRED IN A | | | STORAGE OCCUPANCY. PLEASE INDICATE IF | | | EXISTING FIXTURES ARE LOCATED IN THE | | | BUILDING. SECTION 104.2.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|