| 2005-07-06 00:00:00 | ************* UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SEE COMPUTER SYSTEM SHOWS |
| | |
| | HALSEY& GRIFFITH INC AS OWNERS OF |
| | RECORD. OWNER INFORMATION MUST BE |
| | UPDATED. |
| | PLEASE SEE FOLLOWING COMMENT TO WHEATHER |
| | OR NOT AN OWNER/BUILDER MAY BE PULLED |
| | FOR SCOPE OF WORK AND LOCATED IN A |
| | COMMERCIAL BLDG. |
| | |
| | 2)NOTE: PLEASE SEE BLDG VALUATION IS TO |
| | BE BASED ON ALL LABOR AND MATERIALS AT |
| | FAIR MARKET VALUE. |
| | FBC 104.6.5 |
| | PLEASE SEE BLDG REVIEW COMMENTS. IF |
| | VALUATION IS OVER $25K, THIS MAY NOT BE |
| | DONE BY O/B. |
| | |
| | 3)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH A PANEL |
| | SCHEDULE TO BE SUBMITTED. |
| | PLEASE INCLUDE SIZE OF EXISTING OR NEW |
| | PANEL(S) SERVICE ETC. |
| | PLEASE INCLUDE LOAD CALCUALTIONS FOR |
| | ADDED LOAD TO NEW OR EXISTING. |
| | PLEASE SEE 220.12 FOR TRACK LIGHTING |
| | LOADS. |
| | PLEASE INCLUDE ALL CONTINUOUS LOADS AT |
| | 125%. |
| | 220.10,220.11,220.13,215.3,230.42,215.5 |
| | ETC. |
| | |
| | 4)NOTE: PLEASE SPECIFY USE OF UNIT/ |
| | STORAGE AREA ETC. |
| | PLANS APPEAR TO SHOW AN OFFICE USE OF |
| | SOME TYPE ON UPPER LEVEL? |
| | |
| | 6)NOTE: PLEASE CLARIFY NEW OR EXSITING |
| | SIGN CIRCUIT? 600.5 |
| | |
| | 7)NOTE: PLEASE SEE PLANS MENTIONS NEW |
| | "RECESSED LTS" HOWEVER, PLANS FOR AREA |
| | DO NOT APPEAR TO SHOW NY CEILING |
| | DETAILS? |
| | |
| | 8)NOTE: PLEASE SEE MISSING CONTROL OF |
| | EGRESS LIGHTING FOR STAIRWAY. |
| | LS 101 5-8, 7-9 |
| | SEE POSSIBLE FIRE REVIEW COMMENTS FOR |
| | ANY EM/EXT LTS WHICH MAY BE REQUIRED. |
| | 3-WAY SW? |
| | |
| | 9)NOTE: PLEASE SEE BLDG REVIEW NOTES, |
| | ADDRESS ON PLANS MENTIONS; |
| | "OLD" OKEECHOBEE RD". PLEASE KNOW, THIS |
| | SHOULD READ "OKEECHOBEE RD". |
| | |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| | REVIEWER(S) WHICH MAY HAVE AN AFFECT ON |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL/OLD VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |