| 2005-07-24 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION. |
| | |
| | 3.)PROVIDE A REASONABLE VALUE FOR THIS |
| | JOB OR AN ESTIMATE WILL BE DONE FOR YOU |
| | USING MARSHALL & SWIFT. |
| | |
| | 4.)DECLARE A BUILDING CONSTRUCTION |
| | TYPE FBC CHAPTER 6 AND INDICATE THAT |
| | THIS IS A SPRINKLED BUILDING. |
| | |
| | 5.)AN OWNER/BUILDER CANNOT DO THE WORK |
| | WITH A VALUE OF OVER $25,000 FS489. |
| | |
| | 5.)NO FIRE SPRINKLER INFORMATION WAS |
| | PROVIDED FBC*104.3.1.1(5). |
| | |
| | 6.)DECLARE AN OCCUPANCY FBC CHAPTER 3. |
| | |
| | 7.)THE UPSTAIRS BATHROOM IS TO BE |
| | ADAPTABLE, FBC11-4.1.3(11). |
| | |
| | 8.)PROVIDE AREA CALCULATIONS; EXISTING |
| | SPACE, PROPOSED NEW SPACE. |
| | |
| | 9.)ENERGY CALCS REQUIRED, FBC13. |
| | |
| | 10.) TWO MEANS OF EGRESS FROM THE |
| | MEZZANINE REQUIRED, FBC1005.7.1. |
| | |
| | 11.)SEE FBC1005.7.3.EGRESS STAIRS |
| | MAY BE OPEN WHEN ALL CONDITIONS ARE MET. |
| | ONE OF THE CONDITIONS IS THAT THE SPACE |
| | BENEATH THE MEZZANINE IS OPEN.THIS IS |
| | NOT THE CASE DUE TO THE BATHROOM AND |
| | UTILITY ROOM WALLS PARTIALLY ENCLOSING |
| | THE SPACE UNDER THE MEZZANINE. |
| | |
| | 12.)SEE ALSO FBC1005.7.3(4).THE |
| | MEZZANINE CANNOT BE USED FOR SLEEPING |
| | PURPOSES.PLEASE CLEARLY NOTE ON THE |
| | PLAN IF YOU PLAN TO MEET ALL CONDITIONS |
| | OF FBC1005.7.3. |
| | |
| | 13.)PROVIDE A FLOOR FRAMING PLAN. |
| | |
| | 14.)PROVIDE DETAILS FOR THE HANDRAIL |
| | AND GUARDRAIL, FBC1608.2, FBC1007.2, |
| | FBC1007.5, FBC1015, FBC11-4.9.THE |
| | HANDRAIL EXTENSIONS ARE NOT SHOWN AT THE |
| | BOTTOM OF THE STAIRS ON THE FLOOR PLAN. |
| | |
| | 15.)THE STAIRS ARE TO COMPLY WITH |
| | FBC1007 (FBC1005.7.3).THE TREADS ARE |
| | TO BE A MINIMUM OF 11IN, FBC1007.3.1. |
| | THEY ARE SHOWN AT 10IN. ON THE |
| | STRUCTURALS. |
| | |
| | 16.)SPECIFY FLOOR DESIGN LOAD, FBC16. |