| Plan Review Notes For Permit 05061737 |
| Permit Number |
05061737 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-21 00:00:00 | | | | PLEASE PROVIDE A PANEL DESIGNATION FOR | | | THE CIRCUITS OF ORIGIN, BRANCH CIRCIUT | | | NUMBERS AT THE POLES. | | | ALSO PROVIDE LOAD CALCULATIONS FOR THE | | | PANEL BEING USED INDICATING EXISTING AND | | | PROPOSED LOADS. | | | | | | THE PERSON RESPONSIBLE FOR THE PLAN MUST | | | PRINT NAME AND SIGN PLANS PER 104.2.1 | | | FBC. IF DESIGN PROFESSIONAL IS | | | RESPONSIBLE SEE 471 OR 481 FS, WHICHEVER | | | APPLIES. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|