| Plan Review Notes For Permit 05061714 |
| Permit Number |
05061714 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-07 00:00:00 | ******DENIED****** | | | | | | 1) PLANS SHOW THE ELLIMINATION OF ONE | | | EXIT DOOR. DOES THIS SPACE MEET THE | | | SINGLE EXIT CRITERIA PER NFPA 101, | | | CHAPTER 38? | | | | | | 2) THE DRAWINGS SHOW ONE EMERGENCY | | | LIGHTING FACILITY. WILL THAT PROVIDE | | | ADEQUATE LIGHTING FOR THE ENTIRE SPACE? | | | | | | 3) ACCESS TO 2A-10B,C FIRE EXTINGUISHERS | | | MUST BE PROVIDED TO MEET THE 75' TRAVEL | | | REQUIREMENT. | | | | | | 4) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR THE FIRE SPRINKLER AND | | | FIRE ALARM REMODEL. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 805-6722 OR 835-2951 |
|