| Plan Review Notes For Permit 05061711 |
| Permit Number |
05061711 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-07 00:00:00 | DENIED | | | | | | 1) CLARIFY WHAT IS TO BE DONE WHERE THE | | | FIRE RATED DOOR AND SECTION OF FIRE | | | RATED WALL ARE BEING DEMOED AT THE EXIT | | | CORRIDOR. | | | | | | 2) SPECIFY THE RATING OF THE CORRIDOR | | | WALL AND IF THE BUILDING HAS AN APPROVED | | | AUTOMATIC SPRINKLER SYSTEM. | | | | | | 3) FBC 1004.2 REQUIRES TWO EXITS FROM | | | THE TENNANT SPACE BECAUSE THE TRAVEL | | | DISTANCE TO THE EXIT ACCESS EXCEEDS 75'. | | | | | | 4)FBC 1004.1.4 WHERE 2 OR MORE EXITS OR | | | EXIT ACCESS DOORS ARE REQUIED, AT LEAST | | | 2 OF THE EXIT OR EXIT ACCESS DOORS SHALL | | | BE PLACED A DISTANCE APART EQUAL TO NOT | | | LESS THAN 1/2 OF THE LENGTH OF THE MAX- | | | IMUM OVERALL DIAGONAL DIMENSION OF THE | | | BUILDING OR AREA TO BE SERVED.EXCEPTION | | | #2 ALLOWS THIS TO BE REDUCED TO 1/3 OF | | | THE LENGTH IF BUILDING HAS AN APPROVED | | | AUTOMATIC SPRINKLER SYSTEM. SPECIFY THE | | | TRAVEL DISTANCES TO THE EXITS. DOORS | | | SHOULD BE RELOCATED TO COMPLY WITH THIS | | | SECTION. | | | | | | 5) SPECIFY HOW THE FIRE RATING AND | | | CAPACITY OF THE EXIT CORRIDOR WILL | | | MAINTAINED DURING CONSTRUCTION. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|