| Notes |
| Date |
Text |
| 2009-07-27 16:27:57 | REVISION TO CHANGE PRODUCT APPROVALS IS DENIED. | | | | | | 1) SUBMIT TWO COPIES OF AN EXTERIOR DOOR AND WINDOW | | | SCHEDULE THAT IS COORDINATED WITH THE NUMBERING SYSTEM | | | USED ON THE PLANS. SPECIFY THE DOOR SIZES AND SWINGS, | | | AS WELL AS, THE WINDOW TYPES AND SIZES ON THE SCHEDULE. | | | | | | 2) CIRCLE THE APPROPRIATE WINDOW SIZES, GLASS TYPE AND | | | DESIGN PRESSURES ON THE PRODUCT APPROVALS FOR THE | | | WINDOWS THAT WILL BE INSTALLED. | | | | | | 3) CIRCLE THE DOOR TYPES, GLASS TYPE AND DESIGN | | | PRESSURES FOR THE DOORS THAT WILL BE INSTALLED. | | | | | | 4) CIRCLE THE MULLION SPANS, THE WIDTH AND DESIGN | | | PRESSURE FOR THE MULLIONS THAT WILL BE INSTALLED. | | | | | | 5) SOME OF THE PRODUCT APPROVAL DESIGN PRESSURES ARE | | | LOWER THAN THE REQUIRED OPENING PRESSURES SPECIFIED ON | | | THE PLANS. PROVIDE PRODUCT APPROVALS FOR COMPONENTS | | | WITH ADEQUATE DESIGN PRESSURES. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|