| 2008-01-18 16:46:55 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | GAS PLAN REVIEW: |
| | REVISION DENIED: |
| | |
| | 1. NOTE: AS OF 2/6/07 GAS RISER DIAGRAMS WERE REMOVED |
| | FROM PLANS. PLEASE REFERENCE THE PERMIT INFORMATION |
| | ATTACHED TO THESE COMMENTS INDICATING THIS. A GAS |
| | PERMIT APPLICATION IS REQUIRED FOR THE PROPOSED GAS |
| | SYSTEM. ALICENSED GAS OR PLUMBING CONTRACTOR SHALL |
| | SUBMIT PLANS WITH PERMIT APPLICATION. PLEASE ONLY |
| | SUBMIT PLAN SHEETS PERTAINING TO THE PROPOSED GAS |
| | SYSTEM. TWO COMPLETE SETS OF PLANS ARE NOT REQUIRED FOR |
| | GAS PLANS. PER CHAPTER 1, CITY AMENDMENTS SECTION |
| | *105.1 REQUIRED. |
| | |
| | 2. SHEETS A3.1, A3.2, AND A3.3 FLOOR PLANS HAVE TITLE |
| | BLOCKS WITH COPIED SIGNATURES OF A DESIGN PROFESSIONAL |
| | AND ARE NOT SEALED. PLANS, SPECIFICATIONS, REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND |
| | BEING FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE |
| | AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE |
| | DOCUMENT. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS |
| | FL ADMIN CODE 61G16.003 ARCHITECTS |
| | |
| | 3. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. **THE SUBMITTED PLANS DO NOT HAVE ALL |
| | CUT SECTIONS OF PIPE WITH CORRESPONDING LENGTHS |
| | INDICATED. THIS IS REQUIRED TO VERIFY THE NEXT |
| | COMMENT. |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). **PLEASE CLEARLY INDICATE |
| | THE GAS SYSTEMS LONGEST LENGTH. PER FBC FUEL GAS |
| | SECTION *401.1 SCOPE. |
| | |
| | 5. CLEARLY INDICATE THE LOCATION OF THE REQUIRED MP |
| | REGULATORS ON THE GAS ISOMETRIC RISER DIAGRAM. PER FBC |
| | FUEL GAS SECTION *401.1 SCOPE. |
| | |
| | 6. PROVIDE TWO COPIES OF MANUFACTURER'S SPECFICATION |
| | OF THE MP REGULATORS INDICATING THE MAKE, MODEL NUMBER, |
| | AND A LISTING FROM A NATIONALLY RECOGNIZED TESTING |
| | LABORATORY. |
| | |
| | 7. NOTE: GAS OUTLETS THAT DO NOT CONNECT TO APPLIANCES |
| | (FUTURE) SHALL BE CLEARLY INDICATED AS BEINGCAPPED |
| | GAS TIGHT ON PLANS. IF GAS DELIVERY PRESSURE IS 2 PSI |
| | OR GREATER MP REGULATORE SHALL BE INSTALLED PRIOR TO |
| | FINAL INSPECTION. PER FBC FUEL GAS SECTION *404.12 |
| | OUTLET CLOSERS ANS SECTION *401.1 SCOPE. |
| | |
| | 8. GAS PLANS ARE INDICATING A FUTURE GENERATOR PLEASE |
| | BE AWARE THAT FUTURE GENERATOR GAS PIPING AT OWN RISK, |
| | AND A SEPERATE RESIDENTIAL GENERATOR PERMIT IS REQUIRED |
| | WITH ZONING APPROVAL OF GENERATOR PLACEMENT. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |