2008-01-18 16:46:55PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 REVISION DENIED:
  
 1. NOTE: AS OF 2/6/07 GAS RISER DIAGRAMS WERE REMOVED
 FROM PLANS. PLEASE REFERENCE THE PERMIT INFORMATION
 ATTACHED TO THESE COMMENTS INDICATING THIS. A GAS
 PERMIT APPLICATION IS REQUIRED FOR THE PROPOSED GAS
 SYSTEM. ALICENSED GAS OR PLUMBING CONTRACTOR SHALL
 SUBMIT PLANS WITH PERMIT APPLICATION. PLEASE ONLY
 SUBMIT PLAN SHEETS PERTAINING TO THE PROPOSED GAS
 SYSTEM. TWO COMPLETE SETS OF PLANS ARE NOT REQUIRED FOR
 GAS PLANS. PER CHAPTER 1, CITY AMENDMENTS SECTION
 *105.1 REQUIRED.
  
 2. SHEETS A3.1, A3.2, AND A3.3 FLOOR PLANS HAVE TITLE
 BLOCKS WITH COPIED SIGNATURES OF A DESIGN PROFESSIONAL
 AND ARE NOT SEALED. PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 3. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. **THE SUBMITTED PLANS DO NOT HAVE ALL
 CUT SECTIONS OF PIPE WITH CORRESPONDING LENGTHS
 INDICATED. THIS IS REQUIRED TO VERIFY THE NEXT
 COMMENT.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). **PLEASE CLEARLY INDICATE
 THE GAS SYSTEMS LONGEST LENGTH. PER FBC FUEL GAS
 SECTION *401.1 SCOPE.
  
 5. CLEARLY INDICATE THE LOCATION OF THE REQUIRED MP
 REGULATORS ON THE GAS ISOMETRIC RISER DIAGRAM. PER FBC
 FUEL GAS SECTION *401.1 SCOPE.
  
 6. PROVIDE TWO COPIES OF MANUFACTURER'S SPECFICATION
 OF THE MP REGULATORS INDICATING THE MAKE, MODEL NUMBER,
 AND A LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY.
  
 7. NOTE: GAS OUTLETS THAT DO NOT CONNECT TO APPLIANCES
 (FUTURE) SHALL BE CLEARLY INDICATED AS BEINGCAPPED
 GAS TIGHT ON PLANS. IF GAS DELIVERY PRESSURE IS 2 PSI
 OR GREATER MP REGULATORE SHALL BE INSTALLED PRIOR TO
 FINAL INSPECTION. PER FBC FUEL GAS SECTION *404.12
 OUTLET CLOSERS ANS SECTION *401.1 SCOPE.
  
 8. GAS PLANS ARE INDICATING A FUTURE GENERATOR PLEASE
 BE AWARE THAT FUTURE GENERATOR GAS PIPING AT OWN RISK,
 AND A SEPERATE RESIDENTIAL GENERATOR PERMIT IS REQUIRED
 WITH ZONING APPROVAL OF GENERATOR PLACEMENT.
  
 END OF COMMENTS:
  