Plan Review Notes
Plan Review Notes For Permit 05061696
Permit Number 05061696
Review Stop E
Sequence Number 4
Notes
Date Text
2007-01-17 07:40:38** UNSAT**
  
 ** PLEASE SEE SOME COMMENTS FOR COORDINATION AND
 CHANGES ON PLANS NEED TO BE ADDRESSED.
 PLEASE ALSO SEE NEW COMMENT #4.
  
  
 1) NOTE: PLEASE SEE ON THE PREVIOUS REVIEW IT WAS
 REQUESTED TO SUBMIT THE MANUFACTURE'S SPEC/CUT SHEETS
 FOR THE LIGHTING HOME AUTOMATION SYSTEM WHICH WAS GOING
 TO BE INSTALLED. A COVER LETTER MENTIONS ONE SYSTEM
 WHICH WOULD BE THE LUTRONWHICH MAY BE DONE WITH FOUR
 OR FIVE PANELS AND ONE SYSTEM WHICH COULD BE DONE WITH
 THREE PANELS.
 PLEASE SEE TWO COMPLETELY DIFFERENT PACKAGES FOR THESE
 SYSTEMS WERE SUBMITTED WITH ONLY ONE CONTAINING THE
 LISTING FROM A NRTL. PLEASE SEE THE PACKAGE FOR SYSTEM
 WHICH IS BEING CALLED A CRESTRON DID NOT SEEM IT
 CONTAINED ANY LISTINGS WHICH COULD BE READILY LOCATED
 ON SHEETS PROVIDED.
 ** PLEASE SEE ON THE OTHER HAND THE PLANS SHOWS 4
 LIGHTING CONTROL PANELS WHICH WOULD NOT CORRELATE WITH
 THE STATEMENT ON THE COVER SHEETS WHICH MENTIONS ONLY
 THREE PANELS ARE BEING USED (CRESTRON).
 PLEASE CORRELATE PLANS AND SUBMITTALS AND ONLY SUBMIT
 THE SYSTEM BEING PROPOSED.
 110.3, 90.7
 FBC 106.1.2 ADMIN SECTION.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH REQUESTED THE
 MANUFACTURE'S SPEC/CUT SHEETS FOR THE NEW PROPOSED ATS
 BEING INSTALLED. PLEASE SEE THIS WAS DONE, HOWEVER
 SPECS FOR AN ATS WERE SUBMITTED. PLEASE SEE THE PLANS
 NOW CONTAIN WHAT IS BEING SHOWN AS A MTS, WHICH IS
 BEING DONE?
 PLEASE CORRELATE THESE ALSO.
 90.7, 110.3, FBC 106.1.2 ADMIN SECTION.
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH REQUESTED THE
 AIC RATING OF THE EQUIPMENT BEING INSTALLED. PLEASE SEE
 A NOTE ON PLANS NOW MENTIONS 42K AND THE ELECTRICAL
 CONTRACTOR TO VERIFY WITH FPL ETC BEFORE ORDERING. THIS
 INFORMATION IS SOMETHING THAT IS REQUIRED TO BE
 VERIFIED AT THIS TIME. CONTACT SHOULD BE MADE TO THE
 SERVICE PLANNER FOR THE AREA AND THE INFORMATION CAN BE
 EASILY FOUND OUT.
 PLEASE SEE THAT THE RATINGS ON THE PLANS CALL FOR 42K
 MAIN AND 22K RATED MAINS ON THE LOAD SIDE OF THE HOUSE
 SERVICE MAIN AND 22K RATED BRANCH BREAKERS. ALL OF
 THESE RATINGS ARE PERMITTED AND ARE OK; HOWEVER PLEASE
 KNOW IF THESE RATINGS ARE SHOWN, THEN THIS IS WHAT
 WOULD BE REQUIRED TO BE INSTALLED. PLEASE VERIFY THIS,
 AS THIS IS ONLY BEING NOTED. CONSIDERATION TO THE COST
 OF THE RATED EQUIPMENT AND INSTALLATION OF 22K RATED
 BRANCH BREAKERS ETC MAY WANT TO BE TAKEN INTO
 CONSIDERATION.
 110.9.
  
 4) NOTE:PLEASE KNOW THAT SINCE THE LAST REVIEW OF
 THIS PROJECT, A MEETING WAS HELD AT THE SOUTHERN
 SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY
 INFORMED BY NFPA THAT THE USE OF "SD" FOR SMOKE
 DETECTORS ON PLANS FOR RESIDENTIAL HOMES IS NOT
 ACCEPTABLE WHEN THESE DEVICES ANY ACTUALLY FALL UNDER
 THE DEFINITIONS OF SMOKE ALARMS WHICH WOULD BE SHOWN AS
 "SA"/SMOKE ALARMS".
 THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE
 OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. BY
 THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES; HOWEVER THIS WAS NOT A COMMENT
 FROM THIS AHJ OR REVIEWER BEFORE AS THIS INFORMATION
 WAS MADE AWARE TO ALL OF THE JURISDICTIONS PRESENT,
 MOST OF WHICH HAD ALSO ALWAYS ACCEPTED SD AND THE
 STATED SMOKE DETECTORS.
 IF THE ONLY COMMENT ON THE PLANS WAS THIS, THE PLANS
 WOULD HAVE BEEN REDLINED FOR THE CORRECTIONS AND WOULD
 BE ISSUED WITH REVISIONS TO FOLLOW.
 PLEASE MAKE ADJUSTMENTS FOR THESE AS PLANS ARE COMING
 BACK FOR ZONING COMMENTS AND NOTES ABOVE.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 11.5.1.1, 11.8.3
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]