Plan Review Notes
Plan Review Notes For Permit 05061696
Permit Number 05061696
Review Stop E
Sequence Number 3
Notes
Date Text
2006-06-22 00:00:00******* UNSAT 3RD REVIEW *************
  
 ** PLEASE SEE THERE ARE COMMENTS FROM
 PREVIOUS REVIEW WHICH STILL NEED TO BE
 ADDRESSED AND SOME NEW COMMENTS DUE TO
 PLAN CHANGES.
  
 ** PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM THE PREVIOUS REVIEW AND
 ANY NEW NOTES ARE ADDED AT THE BOTTOM.
  
 ************* UNSAT ******************
  
 1)NOTE: NOTE #1 NO, PLEASE SE A4.2 STILL
 SHOWS THE SAME AS BEFORE.
  
 ** PREVIOUS NOTES**
 PLEASE SEE MAX HEIGHT FOR
 ELECTRICLA METERCAN PER SECTION 6 OF FPL
 SERVICE INSTALLATIONS GUIDELINES SHALL
 BE 6' TO THE CENTER OF METER.
 PLEASE SEE ELEVATION PLANS A4.2 CLEARLY
 SHOW THIS HIGHER.
  
 2)NOTE: NOTE #2 SMAE NOTE, ALSO AS
 ABOVE.
  
 ** PREVIOUS NOTE **
 PLEASE SEE MAX HEIGHT OF
 DISCONNECTING EQUIPMENT/SWITCHES SHALL
 BE 6'7" WITH OUT RESORTING TO LADDERS
 ETC.
 440.11, 100 (DEFINITIONS) ACCESSIBLE
 READILY)404.8
 PLEASE SEE THIS COMMENT IS FOR ALL
 ELECTRICAL EQUIPMENT ON ELEV ON A4.2
  
 3)NOTE: NOTE #3 NO, PLEASE SEE GENERATOR
 LOCATION IS NOT OK. AS OF THIS REVIEW
 PLEASE SEE OTHER NOTES AS EQUIPMENT
 LOCATION CAN NOT BE VERIFIED AS MOST
 GEN'S REQUIRED A MIN OF 3' CLEARENCE ON
 ALL SIDES AND SOME REQUIRE MORE. THERE
 ARE VERY FEW WHICH REQUIRE LESS.
 UNABLE TO VERIFY.
 A/C DISC'S APPEAR TO BE OK AS SHOWN.
  
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE MIN CLEARENCES
 REQUIRED ON SAME ELEVATION FOR ALL A/C
 DISC'S,GENERATOR, METER, ETC.?
 110.26.
  
 4)NOTE: OK.
  
 5)NOTE: OK.
  
 6)NOTE: OK.
  
 7)NOTE: OK.
  
 8)NOTE: OK, HOWEVER SEE NEW NOTES
 PERTAINING TO SD NOTES.
  
 9)NOTE: NOTE #9 NO, PLEASE SEE THAT SOME
 LTS ARE PERMITTED AS LONG AS ON A GFI
 PROTECTED CIRCUIT, HOWEVER PLEASE SEE
 AREAS ALOWWED FOR EXISTING AND NEW.
 PLEASE SEE THE HOUSE IS NEW AND MUST
 MEET ANY REQUIREMENTS FOR NEW
 CONSTRUCTION EVEN IF POOL IS EXISTING.
 PLEASE SEE RECEPTS MAY NOT BE WITHIN
 10FT OF POOL. (NO EXCEPTIONS!)
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE 680.22,680.22B ETC
 FOR MIN CLEARENCES FOR ELECTRICAL
 EQUIPMENT, DEVICES/RECEPTS AND LT
 FIXTURES FROM POOL IN NEW CONSTRUCTION.
 PLEASE SEE POOL HEATER, LTS ETC REDLINED
 ON PLANS.
 PLEASE SEE MIN 10' FOR RECEPTS.
 PLEASE ALSO SEE NOTES FOR LOADS ETC OF
 POOL EQUIPMENT.
 PLEASE NOTE: LT FIXTURES W/IN 5' SHALL
 BE 12' UP.(PLEASE SEE BACK PORCH)?
  
 10)NOTE: OK.
  
 11)NOTE; OK.
  
 12)NOTE: NOTE #12 NO.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SUBMIT COMPLETE
 SPECS/CUT SHEETS FOR LIGHTING CONTROL
 PANELS(AUTOMATION SYSTEM) PLEASE PROVIDE
 SCHEDULING FOR THESE.
 ALL SYSTEMS SHALL BE LISTED BY A NRTL.
 PLEASE ALSO SEE COMMENT PERTAINIG TO
 GEN. LOAD(S).
  
 13)NOTE: OK.
  
 14)NOTE: OK, STILL SHOWS A 24 CIRUCIT
 PANEL YET THIS IS SHOWN AS 200A'S??
  
 15)NOTE: OK.
  
 16)NOTE: OK.
  
 17)NOTE: NOTE #17 NO.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.**NUMBER OF FIX EXCEED GEN LT**
  
 18)NOTE: OK.
  
 19)NOTE: OK.
  
 20)NOTE: OK.
  
 21)NOTE: OK.
  
 22)NOTE: OK.
  
 23)NOTE: OK.
  
 24)NOTE: OK.
  
 25)NOTE: NOTE #25 NO? COULD NOT LOCATE
 THE REQUIRED DISCONNECT. APPEARS TO SHOW
 AN OUTLET/RECEPT ONLY??
  
 * PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING REQUIRED
 EMERGENCY DISCONNETC SWICTH TO BE
 LOCATED ATLEAST 5' FROM SPA/HOT TUB BUT
 NO FURTHER THAN 50'.
 PLEASE SEE 680.41
  
 26)NOTE: OK.
  
 27)NOTE: OK.
  
 28)NOTE: NOTE #28 NO.
 ** PLEASE ALSO KNOW, "K" SWITCH IS NOT
 ACCEPTABLE IN LEIU OF THE REQUIRED
 DISCONNECTING MEANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT COMPLETE
 MANUFACTURE SPECS/CUT SHEETS FOR
 GENERATOR , ATS .
 PLEASE KNOW, GENERATOR CAN BE SUBMITTED
 UNDER SEPARATE PERMIT AT A LATER DATE
 WITH SEPARATE, SURVEY, PLANS, SPECS,
 FEES ETC., HOWEVER, SPECS FOR ATS ARE
 REQUIRED AT THIS TIME FOR REVIEW.
 PLEASE SEE PLANS AND RISER INDICATE THIS
 UNIT AS CONTAINING THE MAIN 1OF 1??
 PLEASE SEE230.76,230.79, 230.91,
 225.31-225.39 ETC
 WHICH REQUIRES THE MANUAL MEANS OF
 DISCONNECT TO BE LOCATED ON THE OUTSIDE
 AND RATED FOR THE LOAD SERVED ETC.
 UNABLE TO VERIFY CODE COMPLIANCE AT THIS
 TIME.
 (THIS WAS REQUESTED ON PREVIOUS REVIEW
 ALSO).
 PLEASE VERIFY IF ATS DOES CONTAIN THE
 MAIN OR DOES NOT AS THIS WILL AFFECT THE
 FOLLOWING.
  
 29)NOTE: OK.
  
 30)NOTE: OK, HOWEVER VERIFY THE #3 BEING
 SHOWN. SEE NEW COMMENTS WITH RESPECT TO
 CONDUIT FILL.
  
 31)NOTE: NOTE #31 NO,PLEASE SEE LOADS
 FOR GEN ON GEN LOAD SUMMARY DO NOT
 INDICATE AN AIR CONDITIONING LOADS??
 PLEASE SEE NOTE MENTIONS TO SHEDD LOADS
 BUT NO DETAIL WAS SUBMITED OR SHOWN.
 PLEASE VERIFY NO A/C LOADS AS THE LOAD
 SHOWN FOR GEN IS SHOWN AT 97A'S.
 PLEASE ALSO VERY HOW THE THE ENTIRE
 SERVICE IS BEING FED YET NOT ALL
 ELECTRICAL WHICH IS BEING SHOWN PANEL
 SCHEDULES ARE ON THE LOAD SUMMARY FOR
 THE GEN??
 215.5
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT COMPLETE LOAD
 SHEDDING DETAILS FOR AUTOMATION SYSTEM
 AS RISER DIAGRAM NOTES GENERATOR SHALL
 BE ADEQUATE FOR THE LOAD TO BE SERVED.
 702.5
 THIS IS REQUIRED AT THIS TIME, UNLESS
 GEN IS NOT PERMITTED AT THIS TIME.
 SEE PREVIOUS NOTES.
  
 32)NOTE: OK.
  
 33)NOTE: OK.
  
 34)NOTE: OK.
  
 35)NOTE: OK.
  
 ***** NEW NOTES *****
  
 36) NOTE: PLEASE SEE SD'S SHALL BE
 INSTALLED PER NFPA-72
 11.5.1.1,11.8.3.5,11.8.3
 PLEASE SEE NOTES MENITONS 12" FROM AIR
 SUPPLIES AND RETURNS. PLEASE SEE NFPA AS
 NOTED ABOVE WHERE NO SD'S AARE PERMITTED
 WITHIN 3' FROM SUPPLIES AND MIN 5' FROM
 RA BASED ON MANUFACTURES SPEC'S.
 PLEASE ADJUST ALL NOTES.
  
 37) NOTE: PLEASE SEE PLANS NOTES IN MANY
 LOCATIONS WITH REFERENCE TO THE "LATEST
 EDITION" OF THE CODE. THIS IS NOT
 PERMITTED AS THE LATEST EDITION WOULD BE
 THE 2004 FBC AND THE LATEST EDITION OF
 THE NEC HAS NOT BEEN ADOPTED BY THE
 STATE OF FLORIDA AS OF YET.
 PLEASE SEE THE FOLLOWING CODES SHALL BE
 REFLECTED ON PLANS AT A MIN ON
 ELECTRICAL SHEETS.
 IF REMAINING UNDER THE 2001 FBC THEN
 THE ELECTRICAL PLANS SHALL REFLECT THE
 2001 FBC, 2002 NFPA-70 (NEC), 2002
 NFPA-72, NFPA-101 2003 AT A MIN.
 PLEASE SEE OTHER REVIEWER(S) AND CODES
 TO APPLY.
  
 38) NOTE: PLEASE SEE A PREVIOUS NOTE
 MENTIONED THAT NOW THE "EQUIPMENT
 GROUNDING CONDUCTORS" ARE NOW SHOWN
 HOWEVER ARE SIZED AT #3'S?? PLEASE KNOW,
 THIS IS OK, ALTHOUGH THEY ARE ONLY
 REQUIRED TO BE SIZED PER 250.122 , BUT
 IF SHOWN ON PLANS THIS SIZE, THEN THIS
 IS WHAT WILL BE REQUIRED.
 ** PLEASE ALSO KNOW, BASED ON FEEDERS
 SHOWNA DN THE EQUIPMENT GROUNDING
 CONDUCTORS NOW SHOWN , PLEASE SEE MAX
 CONDUIT FILL PER TABLES 9, SCH 80.
 PLEASE ADJUST CONDUIT SIZES AS NEEDED.
 215.5
  
 39) NOTE: PLEASE SEE MISSING E-1 ON ONE
 SET OF ELECTRICAL PLANS.
  
 40) NOTE: PLEASE ALSO SEE ONE SET IS
 ALSO MISSING THE "RAISED" SEAL ON SOME
 "S" SHEETS.
 PLEASE KNOW, AS OF DEC 31ST, 2005 IT IS
 NO LONGER ACCEPTABLE USE ENGINEER'S
 SEALS WITH THE WORDING OF "CERTIFICATE".
 PLEASE SEE RULING AS PASSED BY THE
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS
 IN FEB 04 WHICH REQUIRES ALL ENGINEERS
 TO OBTAIN A NEW SEAL CONTAINING THE
 WORDING OF "LICENSE". AN EXTENSION WAS
 GIVEN TO DEC 31ST, 2005.
 SEE BUILDING REVIEW NOTES, THIS IS ONLY
 NOTED IN ELECTRICAL REVIEW FOR
 INFORMATIONAL PURPOSE AS AN FYI.
  
 41) NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO REPEAT
 COMMENTS FOR CODE COMPLIANCE.
 PLEASE SEE THAT ALL COMMENTS FROM
 PREVIOUS REVIEWS MUST BE ADDRESSED.
  
 42) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT, SEE NEW MAINS NOW
 ADDED WHICH DO NOT INDICATERATINGS.
 110.9,215.5
  
 **PLEASE SEE ANY OTHER POSSIBLE COMMENTS
 FROM OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE REMOVE ANY/ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 PLEASE SUBMIT ONE COPY OF OLD SHEETS
 FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
2006-06-21 00:00:00IN ELEC FOR REVIEW.
2006-06-16 00:00:00 
  
  
 SHEET E1 IS MISSING FROM ONE SET OF