| Date |
Text |
| 2006-06-22 00:00:00 | ******* UNSAT 3RD REVIEW ************* |
| | |
| | ** PLEASE SEE THERE ARE COMMENTS FROM |
| | PREVIOUS REVIEW WHICH STILL NEED TO BE |
| | ADDRESSED AND SOME NEW COMMENTS DUE TO |
| | PLAN CHANGES. |
| | |
| | ** PLEASE SEE NOTES BELOW ARE TAKEN |
| | DIRECTLY FROM THE PREVIOUS REVIEW AND |
| | ANY NEW NOTES ARE ADDED AT THE BOTTOM. |
| | |
| | ************* UNSAT ****************** |
| | |
| | 1)NOTE: NOTE #1 NO, PLEASE SE A4.2 STILL |
| | SHOWS THE SAME AS BEFORE. |
| | |
| | ** PREVIOUS NOTES** |
| | PLEASE SEE MAX HEIGHT FOR |
| | ELECTRICLA METERCAN PER SECTION 6 OF FPL |
| | SERVICE INSTALLATIONS GUIDELINES SHALL |
| | BE 6' TO THE CENTER OF METER. |
| | PLEASE SEE ELEVATION PLANS A4.2 CLEARLY |
| | SHOW THIS HIGHER. |
| | |
| | 2)NOTE: NOTE #2 SMAE NOTE, ALSO AS |
| | ABOVE. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE MAX HEIGHT OF |
| | DISCONNECTING EQUIPMENT/SWITCHES SHALL |
| | BE 6'7" WITH OUT RESORTING TO LADDERS |
| | ETC. |
| | 440.11, 100 (DEFINITIONS) ACCESSIBLE |
| | READILY)404.8 |
| | PLEASE SEE THIS COMMENT IS FOR ALL |
| | ELECTRICAL EQUIPMENT ON ELEV ON A4.2 |
| | |
| | 3)NOTE: NOTE #3 NO, PLEASE SEE GENERATOR |
| | LOCATION IS NOT OK. AS OF THIS REVIEW |
| | PLEASE SEE OTHER NOTES AS EQUIPMENT |
| | LOCATION CAN NOT BE VERIFIED AS MOST |
| | GEN'S REQUIRED A MIN OF 3' CLEARENCE ON |
| | ALL SIDES AND SOME REQUIRE MORE. THERE |
| | ARE VERY FEW WHICH REQUIRE LESS. |
| | UNABLE TO VERIFY. |
| | A/C DISC'S APPEAR TO BE OK AS SHOWN. |
| | |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SEE MIN CLEARENCES |
| | REQUIRED ON SAME ELEVATION FOR ALL A/C |
| | DISC'S,GENERATOR, METER, ETC.? |
| | 110.26. |
| | |
| | 4)NOTE: OK. |
| | |
| | 5)NOTE: OK. |
| | |
| | 6)NOTE: OK. |
| | |
| | 7)NOTE: OK. |
| | |
| | 8)NOTE: OK, HOWEVER SEE NEW NOTES |
| | PERTAINING TO SD NOTES. |
| | |
| | 9)NOTE: NOTE #9 NO, PLEASE SEE THAT SOME |
| | LTS ARE PERMITTED AS LONG AS ON A GFI |
| | PROTECTED CIRCUIT, HOWEVER PLEASE SEE |
| | AREAS ALOWWED FOR EXISTING AND NEW. |
| | PLEASE SEE THE HOUSE IS NEW AND MUST |
| | MEET ANY REQUIREMENTS FOR NEW |
| | CONSTRUCTION EVEN IF POOL IS EXISTING. |
| | PLEASE SEE RECEPTS MAY NOT BE WITHIN |
| | 10FT OF POOL. (NO EXCEPTIONS!) |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SEE 680.22,680.22B ETC |
| | FOR MIN CLEARENCES FOR ELECTRICAL |
| | EQUIPMENT, DEVICES/RECEPTS AND LT |
| | FIXTURES FROM POOL IN NEW CONSTRUCTION. |
| | PLEASE SEE POOL HEATER, LTS ETC REDLINED |
| | ON PLANS. |
| | PLEASE SEE MIN 10' FOR RECEPTS. |
| | PLEASE ALSO SEE NOTES FOR LOADS ETC OF |
| | POOL EQUIPMENT. |
| | PLEASE NOTE: LT FIXTURES W/IN 5' SHALL |
| | BE 12' UP.(PLEASE SEE BACK PORCH)? |
| | |
| | 10)NOTE: OK. |
| | |
| | 11)NOTE; OK. |
| | |
| | 12)NOTE: NOTE #12 NO. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SUBMIT COMPLETE |
| | SPECS/CUT SHEETS FOR LIGHTING CONTROL |
| | PANELS(AUTOMATION SYSTEM) PLEASE PROVIDE |
| | SCHEDULING FOR THESE. |
| | ALL SYSTEMS SHALL BE LISTED BY A NRTL. |
| | PLEASE ALSO SEE COMMENT PERTAINIG TO |
| | GEN. LOAD(S). |
| | |
| | 13)NOTE: OK. |
| | |
| | 14)NOTE: OK, STILL SHOWS A 24 CIRUCIT |
| | PANEL YET THIS IS SHOWN AS 200A'S?? |
| | |
| | 15)NOTE: OK. |
| | |
| | 16)NOTE: OK. |
| | |
| | 17)NOTE: NOTE #17 NO. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND.**NUMBER OF FIX EXCEED GEN LT** |
| | |
| | 18)NOTE: OK. |
| | |
| | 19)NOTE: OK. |
| | |
| | 20)NOTE: OK. |
| | |
| | 21)NOTE: OK. |
| | |
| | 22)NOTE: OK. |
| | |
| | 23)NOTE: OK. |
| | |
| | 24)NOTE: OK. |
| | |
| | 25)NOTE: NOTE #25 NO? COULD NOT LOCATE |
| | THE REQUIRED DISCONNECT. APPEARS TO SHOW |
| | AN OUTLET/RECEPT ONLY?? |
| | |
| | * PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING REQUIRED |
| | EMERGENCY DISCONNETC SWICTH TO BE |
| | LOCATED ATLEAST 5' FROM SPA/HOT TUB BUT |
| | NO FURTHER THAN 50'. |
| | PLEASE SEE 680.41 |
| | |
| | 26)NOTE: OK. |
| | |
| | 27)NOTE: OK. |
| | |
| | 28)NOTE: NOTE #28 NO. |
| | ** PLEASE ALSO KNOW, "K" SWITCH IS NOT |
| | ACCEPTABLE IN LEIU OF THE REQUIRED |
| | DISCONNECTING MEANS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT COMPLETE |
| | MANUFACTURE SPECS/CUT SHEETS FOR |
| | GENERATOR , ATS . |
| | PLEASE KNOW, GENERATOR CAN BE SUBMITTED |
| | UNDER SEPARATE PERMIT AT A LATER DATE |
| | WITH SEPARATE, SURVEY, PLANS, SPECS, |
| | FEES ETC., HOWEVER, SPECS FOR ATS ARE |
| | REQUIRED AT THIS TIME FOR REVIEW. |
| | PLEASE SEE PLANS AND RISER INDICATE THIS |
| | UNIT AS CONTAINING THE MAIN 1OF 1?? |
| | PLEASE SEE230.76,230.79, 230.91, |
| | 225.31-225.39 ETC |
| | WHICH REQUIRES THE MANUAL MEANS OF |
| | DISCONNECT TO BE LOCATED ON THE OUTSIDE |
| | AND RATED FOR THE LOAD SERVED ETC. |
| | UNABLE TO VERIFY CODE COMPLIANCE AT THIS |
| | TIME. |
| | (THIS WAS REQUESTED ON PREVIOUS REVIEW |
| | ALSO). |
| | PLEASE VERIFY IF ATS DOES CONTAIN THE |
| | MAIN OR DOES NOT AS THIS WILL AFFECT THE |
| | FOLLOWING. |
| | |
| | 29)NOTE: OK. |
| | |
| | 30)NOTE: OK, HOWEVER VERIFY THE #3 BEING |
| | SHOWN. SEE NEW COMMENTS WITH RESPECT TO |
| | CONDUIT FILL. |
| | |
| | 31)NOTE: NOTE #31 NO,PLEASE SEE LOADS |
| | FOR GEN ON GEN LOAD SUMMARY DO NOT |
| | INDICATE AN AIR CONDITIONING LOADS?? |
| | PLEASE SEE NOTE MENTIONS TO SHEDD LOADS |
| | BUT NO DETAIL WAS SUBMITED OR SHOWN. |
| | PLEASE VERIFY NO A/C LOADS AS THE LOAD |
| | SHOWN FOR GEN IS SHOWN AT 97A'S. |
| | PLEASE ALSO VERY HOW THE THE ENTIRE |
| | SERVICE IS BEING FED YET NOT ALL |
| | ELECTRICAL WHICH IS BEING SHOWN PANEL |
| | SCHEDULES ARE ON THE LOAD SUMMARY FOR |
| | THE GEN?? |
| | 215.5 |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT COMPLETE LOAD |
| | SHEDDING DETAILS FOR AUTOMATION SYSTEM |
| | AS RISER DIAGRAM NOTES GENERATOR SHALL |
| | BE ADEQUATE FOR THE LOAD TO BE SERVED. |
| | 702.5 |
| | THIS IS REQUIRED AT THIS TIME, UNLESS |
| | GEN IS NOT PERMITTED AT THIS TIME. |
| | SEE PREVIOUS NOTES. |
| | |
| | 32)NOTE: OK. |
| | |
| | 33)NOTE: OK. |
| | |
| | 34)NOTE: OK. |
| | |
| | 35)NOTE: OK. |
| | |
| | ***** NEW NOTES ***** |
| | |
| | 36) NOTE: PLEASE SEE SD'S SHALL BE |
| | INSTALLED PER NFPA-72 |
| | 11.5.1.1,11.8.3.5,11.8.3 |
| | PLEASE SEE NOTES MENITONS 12" FROM AIR |
| | SUPPLIES AND RETURNS. PLEASE SEE NFPA AS |
| | NOTED ABOVE WHERE NO SD'S AARE PERMITTED |
| | WITHIN 3' FROM SUPPLIES AND MIN 5' FROM |
| | RA BASED ON MANUFACTURES SPEC'S. |
| | PLEASE ADJUST ALL NOTES. |
| | |
| | 37) NOTE: PLEASE SEE PLANS NOTES IN MANY |
| | LOCATIONS WITH REFERENCE TO THE "LATEST |
| | EDITION" OF THE CODE. THIS IS NOT |
| | PERMITTED AS THE LATEST EDITION WOULD BE |
| | THE 2004 FBC AND THE LATEST EDITION OF |
| | THE NEC HAS NOT BEEN ADOPTED BY THE |
| | STATE OF FLORIDA AS OF YET. |
| | PLEASE SEE THE FOLLOWING CODES SHALL BE |
| | REFLECTED ON PLANS AT A MIN ON |
| | ELECTRICAL SHEETS. |
| | IF REMAINING UNDER THE 2001 FBC THEN |
| | THE ELECTRICAL PLANS SHALL REFLECT THE |
| | 2001 FBC, 2002 NFPA-70 (NEC), 2002 |
| | NFPA-72, NFPA-101 2003 AT A MIN. |
| | PLEASE SEE OTHER REVIEWER(S) AND CODES |
| | TO APPLY. |
| | |
| | 38) NOTE: PLEASE SEE A PREVIOUS NOTE |
| | MENTIONED THAT NOW THE "EQUIPMENT |
| | GROUNDING CONDUCTORS" ARE NOW SHOWN |
| | HOWEVER ARE SIZED AT #3'S?? PLEASE KNOW, |
| | THIS IS OK, ALTHOUGH THEY ARE ONLY |
| | REQUIRED TO BE SIZED PER 250.122 , BUT |
| | IF SHOWN ON PLANS THIS SIZE, THEN THIS |
| | IS WHAT WILL BE REQUIRED. |
| | ** PLEASE ALSO KNOW, BASED ON FEEDERS |
| | SHOWNA DN THE EQUIPMENT GROUNDING |
| | CONDUCTORS NOW SHOWN , PLEASE SEE MAX |
| | CONDUIT FILL PER TABLES 9, SCH 80. |
| | PLEASE ADJUST CONDUIT SIZES AS NEEDED. |
| | 215.5 |
| | |
| | 39) NOTE: PLEASE SEE MISSING E-1 ON ONE |
| | SET OF ELECTRICAL PLANS. |
| | |
| | 40) NOTE: PLEASE ALSO SEE ONE SET IS |
| | ALSO MISSING THE "RAISED" SEAL ON SOME |
| | "S" SHEETS. |
| | PLEASE KNOW, AS OF DEC 31ST, 2005 IT IS |
| | NO LONGER ACCEPTABLE USE ENGINEER'S |
| | SEALS WITH THE WORDING OF "CERTIFICATE". |
| | PLEASE SEE RULING AS PASSED BY THE |
| | FLORIDA BOARD OF PROFESSIONAL ENGINEERS |
| | IN FEB 04 WHICH REQUIRES ALL ENGINEERS |
| | TO OBTAIN A NEW SEAL CONTAINING THE |
| | WORDING OF "LICENSE". AN EXTENSION WAS |
| | GIVEN TO DEC 31ST, 2005. |
| | SEE BUILDING REVIEW NOTES, THIS IS ONLY |
| | NOTED IN ELECTRICAL REVIEW FOR |
| | INFORMATIONAL PURPOSE AS AN FYI. |
| | |
| | 41) NOTE: PLEASE SEE COPY OF FS |
| | 553.80(2)(B) WITH RESPECT TO REPEAT |
| | COMMENTS FOR CODE COMPLIANCE. |
| | PLEASE SEE THAT ALL COMMENTS FROM |
| | PREVIOUS REVIEWS MUST BE ADDRESSED. |
| | |
| | 42) NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT, SEE NEW MAINS NOW |
| | ADDED WHICH DO NOT INDICATERATINGS. |
| | 110.9,215.5 |
| | |
| | **PLEASE SEE ANY OTHER POSSIBLE COMMENTS |
| | FROM OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | ** PLEASE REMOVE ANY/ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | PLEASE SUBMIT ONE COPY OF OLD SHEETS |
| | FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| 2006-06-21 00:00:00 | IN ELEC FOR REVIEW. |
| 2006-06-16 00:00:00 | |
| | |
| | |
| | SHEET E1 IS MISSING FROM ONE SET OF |
| | PLANS. |