| Plan Review Notes For Permit 05061696 |
| Permit Number |
05061696 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-10-11 00:00:00 | DENIED; | | | 1.SECONDARY DRAIN PROTECTION REQUIRED | | | PER. FBC-2001 PLUMBING SEC. 1107.1. | | | 2.HOT WATER CIRCULATION SYSTEM MUST | | | COMPLY WITH FBC 2001 CHAPTER 13. (ENERGY | | | CODE) SEC. 612.1ABC.4 AND 612.1ABC.5 | | | SHOW HOW PUMP WILL TURN OFF TO SAVE | | | ENERGY. HOT WATER PIPING TO BE INSULATED | | | TO SAME ENERGY. | | | 3.WATER RISER DIAGRAM; SHOW COMPLIANCE | | | WITH SEC. 604.9. PLEASE REMOVE ALL | | | SYMBOLS NOT REQUIRED. (AIR CHAMBERS ARE | | | NOT AN APPROVED PRODUCT. | | | 4.JACUZZI DRAIN SHALL BE A FLOOR SINK | | | INSTALLED 1" ABOVE DECK SURFACE, THIS | | | WILL PREVENT RAIN WATER AND WILL CATCH | | | THE INDIRECT DISCHARGE FROM JACUZZI. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 | | | | | | |
|