Plan Review Notes
Plan Review Notes For Permit 05061696
Permit Number 05061696
Review Stop E
Sequence Number 2
Notes
Date Text
2005-10-07 00:00:00************* UNSAT ******************
  
 1)NOTE: PLEASE SEE MAX HEIGHT FOR
 ELECTRICLA METERCAN PER SECTION 6 OF FPL
 SERVICE INSTALLATIONS GUIDELINES SHALL
 BE 6' TO THE CENTER OF METER.
 PLEASE SEE ELEVATION PLANS A4.2 CLEARLY
 SHOW THIS HIGHER.
  
 2)NOTE: PLEASE SEE MAX HEIGHT OF
 DISCONNECTING EQUIPMENT/SWITCHES SHALL
 BE 6'7" WITH OUT RESORTING TO LADDERS
 ETC.
 440.11, 100 (DEFINITIONS) ACCESSIBLE
 READILY)404.8
 PLEASE SEE THIS COMMENT IS FOR ALL
 ELECTRICAL EQUIPMENT ON ELEV ON A4.2
  
 3)NOTE: PLEASE SEE MIN CLEARENCES
 REQUIRED ON SAME ELEVATION FOR ALL A/C
 DISC'S,GENERATOR, METER, ETC.?
 110.26.
  
 4)NOTE: PLEASE SEE MISSING DISC'S FOR
 POOL EQUIPMENT ON THAT SIDE OF HOUSE.
 PLANS MENTIONS POOL EXISTING? PLEASE
 ALSO SEE LOAD CALCULATIONS MENTIONS EST
 LOAD? IF EXISTING, LOADS SHOULD BE
 KNOWN.
  
 5)NOTE: PLEASE SEE CABANA BLDG IS NOT
 PART OF MAIN HOUSE AND IS REQUIRED TO
 HAVE DISCONNECTING MEANS PER 225.31.
 PLEASE ALSO SEE GROUPING PER 225.34,
 PLEASE KNOW, IF MORE THAN 6 INDIVIDUAL
 CIRCUITS AT THIS DETACHED BLDG, A PANEL
 WILL BE REQUIRED AND A DISCONNECT OR MCB
 PANEL WILL BE REQUIRED.
 PLEASE ADJUST RISER DIAGRAM AND SEE NEXT
 NOTE.
  
 6)NOTE: PLEASE SEE 250.32 FOR GROUNDING
 ELECTRODE SYSTEM AT DETACHED BLDG.
  
 7)NOTE: PLEASE SEE MISSING SW AND LT AT
 CABANA BATH PER 210.70
  
 8)NOTE: PLEASE SEE SD'S WILL BE REQUIRED
 AT CABANA AT FIRST AND SECOND FLRS.
 FIRST FLR IS CONSIDERED AN ADAPTABLE
 SLEEPING RM WITH BATH RM.
 PLEASE ALSO SEE SD'S REQUIRED ON ALL
 LEVELS OF A MULTI-LEVEL BLDG.
 NFPA-72 11.5.1.1
  
 9)NOTE: PLEASE SEE 680.22,680.22B ETC
 FOR MIN CLEARENCES FOR ELECTRICAL
 EQUIPMENT, DEVICES/RECEPTS AND LT
 FIXTURES FROM POOL IN NEW CONSTRUCTION.
 PLEASE SEE POOL HEATER, LTS ETC REDLINED
 ON PLANS.
 PLEASE SEE MIN 10' FOR RECEPTS.
 PLEASE ALSO SEE NOTES FOR LOADS ETC OF
 POOL EQUIPMENT.
 PLEASE NOTE: LT FIXTURES W/IN 5' SHALL
 BE 12' UP.(PLEASE SEE BACK PORCH)?
  
 10)NOTE: PLEASE SEE PANEL SCHEDULE "C"
 INDICATES "POOL EQUIPMENT" AS 14.2KW,
 HOWEVER PLEASE SEE THAT ALL CONTINUOUS
 LOADS ARE FIGURED AT 125%.
 PLEASE SEE THIS APPEARS TO ONLY FEED ONE
 PIECE OF EQUIPMENT? COOULD NOT LOCATE
 POOL PUMP, LT ETC. IS THERE A POOL PANEL
 AND THE 2P 70A A SUB-FEED?
 PLEASE SEE IF THIS IS NOT ALREADY FIGURE
 AT CONTINUOUS LOAD, 70A OCP WOULD NOT BE
 LARGE ENOUGH. 215.3,230.42,680.9 ETC.
  
 11)NOTE; PLEASE SEE BLDG PLANS INDICATE
 A "WASHER AND DRYER" IN GARAGE AS
 FUTURE, HOWEVER ELECTRICAL PLANS SEEM TO
 SHOW THESE , BUT NOT NOTED FOR FUTURE,
 NOW ? NO ELECTRICAL DEVICES SHOWN.
 IF THESE UNITS ARE NOT GOING TO BE
 INSTALLED, PLEASE REMOVE FROM PLANS.
  
 12)NOTE: PLEASE SUBMIT COMPLETE
 SPECS/CUT SHEETS FOR LIGHTING CONTROL
 PANELS(AUTOMATION SYSTEM) PLEASE PROVIDE
 SCHEDULING FOR THESE.
 ALL SYSTEMS SHALL BE LISTED BY A NRTL.
 PLEASE ALSO SEE COMMENT PERTAINIG TO
 GEN. LOAD(S).
  
 13)NOTE: PLEASE SEE PLANS CALL FOR
 CIRCUITING OF WHAT APPEARS TO BE THE
 ELEVATOR ON PANEL C-25, 27, HOWEVER
 PLEASE SEE PANEL "C" IS BEING SHOWN WITH
 ONLY 24 CIRCUITS??
 PLEASE SEE PANEL "D" SEEMS TO SHOW THIS.
 (MISPRINT).
  
 14)NOTE: PLEASE VERIFY CIRCUITING SHOWN
 FOR PANEL "C" AS BEING A 24 CIRCUIT
 PANEL AND ALSO BEING 200A?
 215.5
  
 15)NOTE: PLEASE SEE MISSING EGRESS
 LIGHTING CONTROL FROM GARAGE TO FRONT
 PORCH AREA. 210.70 (3-WAY?)
  
 16)NOTE: PLEASE CLARIFY CABANA LTS WHICH
 SEEM TO BE SHOWN AS "RECESSED LT"
 FIXTURES. PLEASE SEE PLANS CALL FOR A
 "WOOD DECK" ABOVE WHICH DOES SEEM TO
 DETAIL WHEATHER PROTECTION. AN OUTDOOR
 WP RECESSED IS NOT KNOWN OF AT THIS
 TIME. PLEASE ALSO VEIFY FAN LOCATION.
 IF THESE ARE OUTDOOR RAINTIGHT FIXTURES,
 PLEASE PROVIDE INFORMATION.
 90.7,110.3
  
 17)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.**NUMBER OF FIX EXCEED GEN LT**
  
 18)NOTE: PLEASE SEE MISSING RECEPT ON
 2ND FLR PASSAGE/HALLWAY. 210.52H
 REDLINED ON PLANS.
  
 19)NOTE: PLEASE CLARIFY RECEPT (B-7)
 LAUNDRY RECEPT SHOWN BEHIND DRYER?
 THIS IS ONLY A NOTE.
  
 20)NOTE: PLEASE SEE 2ND FLR, ROOM
 LOCATED OUTSIDE "DUMB WAITER", ON A3.2
 THIS SHOWS A "BAR RM" WITH A FRIG ETC,
 HOWEVER ELECTRICAL PLANS DO NOT IDENTIFY
 THIS ROOM AND NO RECEPT IS SHOWN FOR
 FRIG? PLEASE ADJUST , PANEL
 SCHEDULE,LOADS ETC.
 215.5
  
 21)NOTE: PLEASE INDICATE CIRCUIT FOR
 "JACUZZI TUB" LOCATED IN MASTER BATH RM.
 215.5
 PLEASE ADJUST LOAD CALCS, PANEL SCHEDULE
 ETC AS A JACUZZI RECEPT IS SHOWN ON
 PANEL "D" TO ROOF UNIT>
  
 22)NOTE: PLEASE SEE RECEPT SHOWN AT BAR
 ON 3RD FLR IS REQUIRED TO BE GFI LOCATED
 WITH IN 6' OF WET BAR SINK. 210.8A7
  
 23)NOTE: PLEASE IDENTIFY A DISCONNECT
 SWITCH BEING SHOWN AT 3RD LEVEL, TILED
 TERRACE AREA?
 NO CIRCUITING , ??
  
 24)NOTE: PLEASE SEE MIN CLEARENCES
 REQUIRED FOR LIGHTING FIXTURE(SHOWN AS
 FUTURE) (J-BOXES) CIRCUITING TO D-6 AT
 3RD FLR AREA. PLEASE SEE TWO BOXES WITH
 IN ZONE OF JACUZZI/HOT TUB.
 680.40
  
 25)NOTE: PLEASE SEE MISSING REQUIRED
 EMERGENCY DISCONNETC SWICTH TO BE
 LOCATED ATLEAST 5' FROM SPA/HOT TUB BUT
 NO FURTHER THAN 50'.
 PLEASE SEE 680.41
  
 26)NOTE: PLEASE CORRELATE PLANS, PANEL
 CIRCUITING FOR WHAT APPEARS TO BE A A/C
 UNIT AT 3RD FLR??
 PLEASE SEE PLANS SHOWS A "D-7" , HOWEVER
 PANEL SCHEDULE SHOWS CIRCUIT "D-7,9"??
 FOR AN A/C UNIT??
 215.5
 IS THIS A WALL UNIT? PLUG-IN? DISC?
 440.11
  
 27)NOTE: PLEASE SEE A MEANS OF EGRESS
 LTIGHTING CONTROL SWITCH IS REQUIRED AT
 (4TH) LEVEL ROOF TILED AREA DOWN TO 3RD
 LEVEL. PLEASE SHOW AS WP.210.70
 (3-WAY)??
  
 28)NOTE: PLEASE SUBMIT COMPLETE
 MANUFACTURE SPECS/CUT SHEETS FOR
 GENERATOR , ATS .
 PLEASE KNOW, GENERATOR CAN BE SUBMITTED
 UNDER SEPARATE PERMIT AT A LATER DATE
 WITH SEPARATE, SURVEY, PLANS, SPECS,
 FEES ETC., HOWEVER, SPECS FOR ATS ARE
 REQUIRED AT THIS TIME FOR REVIEW.
 PLEASE SEE PLANS AND RISER INDICATE THIS
 UNIT AS CONTAINING THE MAIN 1OF 1??
 PLEASE SEE230.76,230.79, 230.91 ETC
 WHICH REQUIRES THE MANUAL MEANS OF
 DISCONNECT TO BE LOCATED ON THE OUTSIDE
 AND RATED FOR THE LOAD SERVED ETC.
 UNABLE TO VERIFY CODE COMPLIANCE AT THIS
 TIME.
 (THIS WAS REQUESTED ON PREVIOUS REVIEW
 ALSO).
 PLEASE VERIFY IF ATS DOES CONTAIN THE
 MAIN OR DOES NOT AS THIS WILL AFFECT THE
 FOLLOWING.
  
 29)NOTE: PLEASE SEE 250.24 FOR THE
 LOCATION PERMITTED FOR THE GROUNDING
 ELECTRODE SYSTEM.
 (IF THERE IS ANY QUESTION, GROUNDING
 ELECTRODE CONDUCTOR MAY BE LOCATED AT
 METER.
  
 30)NOTE: PLEASE ALSO SEE MISSING
 EQUIPMENT GROUNDING CONDUCTOR BETWEEN
 THE FIRST MEANS OF DISCONNECT(?) AND
 GUTTER.
 250.110,250.122,250.24
  
 31)NOTE: PLEASE SUBMIT COMPLETE LOAD
 SHEDDING DETAILS FOR AUTOMATION SYSTEM
 AS RISER DIAGRAM NOTES GENERATOR SHALL
 BE ADEQUATE FOR THE LOAD TO BE SERVED.
 702.5
 THIS IS REQUIRED AT THIS TIME, UNLESS
 GEN IS NOT PERMITTED AT THIS TIME.
 SEE PREVIOUS NOTES.
  
 32)NOTE: PLEASE SEE PANEL SCHEDULE "D",
 CIRCUITS 10/12 WHICH SHOWS A FEED TO A
 "SPA" , HOWEVER THIS COULD NOT BE LCATED
 ON PLANS??
 215.5
  
 33)NOTE: PLEASE SEE LOAD CALCULATIONS
 WHICH INDICATE 10,000 SQ FT FIGURED FOR
 HOUSE , YET APPLICATION AND BLDG PLANS
 DO NOT CORRELATE WITH THIS NUMBER??
 215.5
  
 34)NOTE: PLEASE BE SURE ALL DEDICATE
 ITEMS ON PANEL SCHEDULES ARE FIGURED
 INTO LOAD CALCAULTIONS. SEE PREVIOUS
 NOTES WITH RESPECT TO FRIG, POOL
 EQUIPMENT ETC.
 PLEASE SEE A DEDICATED LAUNDRY
 LOAD/CIRCUIT IS SHOWN ON PANEL "B",
 HOWEVER THIS NOT FIGURED INTO LOAD
 CALCULATIONS FOR MAIN HOUSE.
 PLEASE SEE EXTERIOR LTS ON PANEL "D" IS
 SHOWNAT 6.3 KW WHICH IS ABOVE 3 WATTS
 PER SQ FT ALREADY FIGURED??
 215.5
  
 35)NOTE: PLEASE SEE LOCATION OF TVSS
 SHOWN AT LOCATION WHICH APPEARS TO BE
 TAPPED INTO THE PIPE LOCATED BETWEEN
 GUTTER AND ATS??
 PLEASE SEE 285.21 FOR LOCATIONS
 PERMITTED.
  
 **PLEASE SEE ANY OTHER POSSIBLE COMMENTS
 FROM OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE REMOVE ANY/ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 PLEASE SUBMIT ONE COPY OF OLD SHEETS
 FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  
  
  