| 2005-10-07 00:00:00 | ************* UNSAT ****************** |
| | |
| | 1)NOTE: PLEASE SEE MAX HEIGHT FOR |
| | ELECTRICLA METERCAN PER SECTION 6 OF FPL |
| | SERVICE INSTALLATIONS GUIDELINES SHALL |
| | BE 6' TO THE CENTER OF METER. |
| | PLEASE SEE ELEVATION PLANS A4.2 CLEARLY |
| | SHOW THIS HIGHER. |
| | |
| | 2)NOTE: PLEASE SEE MAX HEIGHT OF |
| | DISCONNECTING EQUIPMENT/SWITCHES SHALL |
| | BE 6'7" WITH OUT RESORTING TO LADDERS |
| | ETC. |
| | 440.11, 100 (DEFINITIONS) ACCESSIBLE |
| | READILY)404.8 |
| | PLEASE SEE THIS COMMENT IS FOR ALL |
| | ELECTRICAL EQUIPMENT ON ELEV ON A4.2 |
| | |
| | 3)NOTE: PLEASE SEE MIN CLEARENCES |
| | REQUIRED ON SAME ELEVATION FOR ALL A/C |
| | DISC'S,GENERATOR, METER, ETC.? |
| | 110.26. |
| | |
| | 4)NOTE: PLEASE SEE MISSING DISC'S FOR |
| | POOL EQUIPMENT ON THAT SIDE OF HOUSE. |
| | PLANS MENTIONS POOL EXISTING? PLEASE |
| | ALSO SEE LOAD CALCULATIONS MENTIONS EST |
| | LOAD? IF EXISTING, LOADS SHOULD BE |
| | KNOWN. |
| | |
| | 5)NOTE: PLEASE SEE CABANA BLDG IS NOT |
| | PART OF MAIN HOUSE AND IS REQUIRED TO |
| | HAVE DISCONNECTING MEANS PER 225.31. |
| | PLEASE ALSO SEE GROUPING PER 225.34, |
| | PLEASE KNOW, IF MORE THAN 6 INDIVIDUAL |
| | CIRCUITS AT THIS DETACHED BLDG, A PANEL |
| | WILL BE REQUIRED AND A DISCONNECT OR MCB |
| | PANEL WILL BE REQUIRED. |
| | PLEASE ADJUST RISER DIAGRAM AND SEE NEXT |
| | NOTE. |
| | |
| | 6)NOTE: PLEASE SEE 250.32 FOR GROUNDING |
| | ELECTRODE SYSTEM AT DETACHED BLDG. |
| | |
| | 7)NOTE: PLEASE SEE MISSING SW AND LT AT |
| | CABANA BATH PER 210.70 |
| | |
| | 8)NOTE: PLEASE SEE SD'S WILL BE REQUIRED |
| | AT CABANA AT FIRST AND SECOND FLRS. |
| | FIRST FLR IS CONSIDERED AN ADAPTABLE |
| | SLEEPING RM WITH BATH RM. |
| | PLEASE ALSO SEE SD'S REQUIRED ON ALL |
| | LEVELS OF A MULTI-LEVEL BLDG. |
| | NFPA-72 11.5.1.1 |
| | |
| | 9)NOTE: PLEASE SEE 680.22,680.22B ETC |
| | FOR MIN CLEARENCES FOR ELECTRICAL |
| | EQUIPMENT, DEVICES/RECEPTS AND LT |
| | FIXTURES FROM POOL IN NEW CONSTRUCTION. |
| | PLEASE SEE POOL HEATER, LTS ETC REDLINED |
| | ON PLANS. |
| | PLEASE SEE MIN 10' FOR RECEPTS. |
| | PLEASE ALSO SEE NOTES FOR LOADS ETC OF |
| | POOL EQUIPMENT. |
| | PLEASE NOTE: LT FIXTURES W/IN 5' SHALL |
| | BE 12' UP.(PLEASE SEE BACK PORCH)? |
| | |
| | 10)NOTE: PLEASE SEE PANEL SCHEDULE "C" |
| | INDICATES "POOL EQUIPMENT" AS 14.2KW, |
| | HOWEVER PLEASE SEE THAT ALL CONTINUOUS |
| | LOADS ARE FIGURED AT 125%. |
| | PLEASE SEE THIS APPEARS TO ONLY FEED ONE |
| | PIECE OF EQUIPMENT? COOULD NOT LOCATE |
| | POOL PUMP, LT ETC. IS THERE A POOL PANEL |
| | AND THE 2P 70A A SUB-FEED? |
| | PLEASE SEE IF THIS IS NOT ALREADY FIGURE |
| | AT CONTINUOUS LOAD, 70A OCP WOULD NOT BE |
| | LARGE ENOUGH. 215.3,230.42,680.9 ETC. |
| | |
| | 11)NOTE; PLEASE SEE BLDG PLANS INDICATE |
| | A "WASHER AND DRYER" IN GARAGE AS |
| | FUTURE, HOWEVER ELECTRICAL PLANS SEEM TO |
| | SHOW THESE , BUT NOT NOTED FOR FUTURE, |
| | NOW ? NO ELECTRICAL DEVICES SHOWN. |
| | IF THESE UNITS ARE NOT GOING TO BE |
| | INSTALLED, PLEASE REMOVE FROM PLANS. |
| | |
| | 12)NOTE: PLEASE SUBMIT COMPLETE |
| | SPECS/CUT SHEETS FOR LIGHTING CONTROL |
| | PANELS(AUTOMATION SYSTEM) PLEASE PROVIDE |
| | SCHEDULING FOR THESE. |
| | ALL SYSTEMS SHALL BE LISTED BY A NRTL. |
| | PLEASE ALSO SEE COMMENT PERTAINIG TO |
| | GEN. LOAD(S). |
| | |
| | 13)NOTE: PLEASE SEE PLANS CALL FOR |
| | CIRCUITING OF WHAT APPEARS TO BE THE |
| | ELEVATOR ON PANEL C-25, 27, HOWEVER |
| | PLEASE SEE PANEL "C" IS BEING SHOWN WITH |
| | ONLY 24 CIRCUITS?? |
| | PLEASE SEE PANEL "D" SEEMS TO SHOW THIS. |
| | (MISPRINT). |
| | |
| | 14)NOTE: PLEASE VERIFY CIRCUITING SHOWN |
| | FOR PANEL "C" AS BEING A 24 CIRCUIT |
| | PANEL AND ALSO BEING 200A? |
| | 215.5 |
| | |
| | 15)NOTE: PLEASE SEE MISSING EGRESS |
| | LIGHTING CONTROL FROM GARAGE TO FRONT |
| | PORCH AREA. 210.70 (3-WAY?) |
| | |
| | 16)NOTE: PLEASE CLARIFY CABANA LTS WHICH |
| | SEEM TO BE SHOWN AS "RECESSED LT" |
| | FIXTURES. PLEASE SEE PLANS CALL FOR A |
| | "WOOD DECK" ABOVE WHICH DOES SEEM TO |
| | DETAIL WHEATHER PROTECTION. AN OUTDOOR |
| | WP RECESSED IS NOT KNOWN OF AT THIS |
| | TIME. PLEASE ALSO VEIFY FAN LOCATION. |
| | IF THESE ARE OUTDOOR RAINTIGHT FIXTURES, |
| | PLEASE PROVIDE INFORMATION. |
| | 90.7,110.3 |
| | |
| | 17)NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND.**NUMBER OF FIX EXCEED GEN LT** |
| | |
| | 18)NOTE: PLEASE SEE MISSING RECEPT ON |
| | 2ND FLR PASSAGE/HALLWAY. 210.52H |
| | REDLINED ON PLANS. |
| | |
| | 19)NOTE: PLEASE CLARIFY RECEPT (B-7) |
| | LAUNDRY RECEPT SHOWN BEHIND DRYER? |
| | THIS IS ONLY A NOTE. |
| | |
| | 20)NOTE: PLEASE SEE 2ND FLR, ROOM |
| | LOCATED OUTSIDE "DUMB WAITER", ON A3.2 |
| | THIS SHOWS A "BAR RM" WITH A FRIG ETC, |
| | HOWEVER ELECTRICAL PLANS DO NOT IDENTIFY |
| | THIS ROOM AND NO RECEPT IS SHOWN FOR |
| | FRIG? PLEASE ADJUST , PANEL |
| | SCHEDULE,LOADS ETC. |
| | 215.5 |
| | |
| | 21)NOTE: PLEASE INDICATE CIRCUIT FOR |
| | "JACUZZI TUB" LOCATED IN MASTER BATH RM. |
| | 215.5 |
| | PLEASE ADJUST LOAD CALCS, PANEL SCHEDULE |
| | ETC AS A JACUZZI RECEPT IS SHOWN ON |
| | PANEL "D" TO ROOF UNIT> |
| | |
| | 22)NOTE: PLEASE SEE RECEPT SHOWN AT BAR |
| | ON 3RD FLR IS REQUIRED TO BE GFI LOCATED |
| | WITH IN 6' OF WET BAR SINK. 210.8A7 |
| | |
| | 23)NOTE: PLEASE IDENTIFY A DISCONNECT |
| | SWITCH BEING SHOWN AT 3RD LEVEL, TILED |
| | TERRACE AREA? |
| | NO CIRCUITING , ?? |
| | |
| | 24)NOTE: PLEASE SEE MIN CLEARENCES |
| | REQUIRED FOR LIGHTING FIXTURE(SHOWN AS |
| | FUTURE) (J-BOXES) CIRCUITING TO D-6 AT |
| | 3RD FLR AREA. PLEASE SEE TWO BOXES WITH |
| | IN ZONE OF JACUZZI/HOT TUB. |
| | 680.40 |
| | |
| | 25)NOTE: PLEASE SEE MISSING REQUIRED |
| | EMERGENCY DISCONNETC SWICTH TO BE |
| | LOCATED ATLEAST 5' FROM SPA/HOT TUB BUT |
| | NO FURTHER THAN 50'. |
| | PLEASE SEE 680.41 |
| | |
| | 26)NOTE: PLEASE CORRELATE PLANS, PANEL |
| | CIRCUITING FOR WHAT APPEARS TO BE A A/C |
| | UNIT AT 3RD FLR?? |
| | PLEASE SEE PLANS SHOWS A "D-7" , HOWEVER |
| | PANEL SCHEDULE SHOWS CIRCUIT "D-7,9"?? |
| | FOR AN A/C UNIT?? |
| | 215.5 |
| | IS THIS A WALL UNIT? PLUG-IN? DISC? |
| | 440.11 |
| | |
| | 27)NOTE: PLEASE SEE A MEANS OF EGRESS |
| | LTIGHTING CONTROL SWITCH IS REQUIRED AT |
| | (4TH) LEVEL ROOF TILED AREA DOWN TO 3RD |
| | LEVEL. PLEASE SHOW AS WP.210.70 |
| | (3-WAY)?? |
| | |
| | 28)NOTE: PLEASE SUBMIT COMPLETE |
| | MANUFACTURE SPECS/CUT SHEETS FOR |
| | GENERATOR , ATS . |
| | PLEASE KNOW, GENERATOR CAN BE SUBMITTED |
| | UNDER SEPARATE PERMIT AT A LATER DATE |
| | WITH SEPARATE, SURVEY, PLANS, SPECS, |
| | FEES ETC., HOWEVER, SPECS FOR ATS ARE |
| | REQUIRED AT THIS TIME FOR REVIEW. |
| | PLEASE SEE PLANS AND RISER INDICATE THIS |
| | UNIT AS CONTAINING THE MAIN 1OF 1?? |
| | PLEASE SEE230.76,230.79, 230.91 ETC |
| | WHICH REQUIRES THE MANUAL MEANS OF |
| | DISCONNECT TO BE LOCATED ON THE OUTSIDE |
| | AND RATED FOR THE LOAD SERVED ETC. |
| | UNABLE TO VERIFY CODE COMPLIANCE AT THIS |
| | TIME. |
| | (THIS WAS REQUESTED ON PREVIOUS REVIEW |
| | ALSO). |
| | PLEASE VERIFY IF ATS DOES CONTAIN THE |
| | MAIN OR DOES NOT AS THIS WILL AFFECT THE |
| | FOLLOWING. |
| | |
| | 29)NOTE: PLEASE SEE 250.24 FOR THE |
| | LOCATION PERMITTED FOR THE GROUNDING |
| | ELECTRODE SYSTEM. |
| | (IF THERE IS ANY QUESTION, GROUNDING |
| | ELECTRODE CONDUCTOR MAY BE LOCATED AT |
| | METER. |
| | |
| | 30)NOTE: PLEASE ALSO SEE MISSING |
| | EQUIPMENT GROUNDING CONDUCTOR BETWEEN |
| | THE FIRST MEANS OF DISCONNECT(?) AND |
| | GUTTER. |
| | 250.110,250.122,250.24 |
| | |
| | 31)NOTE: PLEASE SUBMIT COMPLETE LOAD |
| | SHEDDING DETAILS FOR AUTOMATION SYSTEM |
| | AS RISER DIAGRAM NOTES GENERATOR SHALL |
| | BE ADEQUATE FOR THE LOAD TO BE SERVED. |
| | 702.5 |
| | THIS IS REQUIRED AT THIS TIME, UNLESS |
| | GEN IS NOT PERMITTED AT THIS TIME. |
| | SEE PREVIOUS NOTES. |
| | |
| | 32)NOTE: PLEASE SEE PANEL SCHEDULE "D", |
| | CIRCUITS 10/12 WHICH SHOWS A FEED TO A |
| | "SPA" , HOWEVER THIS COULD NOT BE LCATED |
| | ON PLANS?? |
| | 215.5 |
| | |
| | 33)NOTE: PLEASE SEE LOAD CALCULATIONS |
| | WHICH INDICATE 10,000 SQ FT FIGURED FOR |
| | HOUSE , YET APPLICATION AND BLDG PLANS |
| | DO NOT CORRELATE WITH THIS NUMBER?? |
| | 215.5 |
| | |
| | 34)NOTE: PLEASE BE SURE ALL DEDICATE |
| | ITEMS ON PANEL SCHEDULES ARE FIGURED |
| | INTO LOAD CALCAULTIONS. SEE PREVIOUS |
| | NOTES WITH RESPECT TO FRIG, POOL |
| | EQUIPMENT ETC. |
| | PLEASE SEE A DEDICATED LAUNDRY |
| | LOAD/CIRCUIT IS SHOWN ON PANEL "B", |
| | HOWEVER THIS NOT FIGURED INTO LOAD |
| | CALCULATIONS FOR MAIN HOUSE. |
| | PLEASE SEE EXTERIOR LTS ON PANEL "D" IS |
| | SHOWNAT 6.3 KW WHICH IS ABOVE 3 WATTS |
| | PER SQ FT ALREADY FIGURED?? |
| | 215.5 |
| | |
| | 35)NOTE: PLEASE SEE LOCATION OF TVSS |
| | SHOWN AT LOCATION WHICH APPEARS TO BE |
| | TAPPED INTO THE PIPE LOCATED BETWEEN |
| | GUTTER AND ATS?? |
| | PLEASE SEE 285.21 FOR LOCATIONS |
| | PERMITTED. |
| | |
| | **PLEASE SEE ANY OTHER POSSIBLE COMMENTS |
| | FROM OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | ** PLEASE REMOVE ANY/ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | PLEASE SUBMIT ONE COPY OF OLD SHEETS |
| | FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |