Notes
Date Text
2005-07-23 00:00:00DENIED;
 1.SANITARY RISER DIAGRAM;
 A.VENT AND WASTE PIPING SYSTEM IS NOT
 REQUIRED IN A HOSE SYSTEM.
 B.FIRST FLOOR BATHROOM NOT TIED TO
 BUILDING DRAIN.
 C.WASHING MACHINE ON FIRST FLOOR NOT
 VENTED.
 D.ALL SANITARY DRAINAGE PIPING SHALL
 BE SIZED FOR FUTURE FIXTURES,(3" FLOOR
 DRAIN FOR JACUZZI)
 E.2-WAY CLEANOUT REQUIRED FOR CABANA
 3' OUTSIDE BUILDING.
 2.SHOW SIZE OR ROOF SCUPPERS AND
 MATERIAL USED. ALSO SHOW TOTAL SQUIRE
 FOOTAGE CAULKS. PER CHAPTER 11 FBC
 PLUMBING.
 GAS;
 1.SEE "GAS PERMIT APPLICATION
 REQUIREMENTS" SHEET. COMPLY WITH ITEMS
 1, 3, 4, 7, AND 9.
 2.ALL FUTURE GAS EQUIPMENT SHOULD BE
 ADDED TO CAULCULATIONS SO GAS PIPE
 SIZEDOES NOT CHANGE WHEN EQUIPMENT IS
 ADDED.
 3.IS GENERATOR NAT. GAS IF SO CAULKS
 SHOULD BE INCLUDED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  
  
  