| Plan Review Notes For Permit 05061696 |
| Permit Number |
05061696 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-10-11 00:00:00 | DENIED; | | | 1.PLEASE SIZE ALL CUT OFF PIPE. (SECOND | | | REQUEST) | | | 2.SHOW FUTURE WATER HEATER ON RISER | | | DIAGRAM. PIPE SHOULD BE INSTALLED WITH | | | SHUTOFFVALVE AND PLUG IF NOT USED. | | | 3.PLESE SUBMIT MANUFACTORS CUT SHEETS | | | FOR GAS LAMPS AND GENERATOR. | | | 4.MOST BLACK IRON INSTALLATIONS ARE | | | WELDED 2" AND LARGER, UNDER 2" IS SCREW | | | PIPE. IS ALL PIPE TO BE WELDED? | | | 5. PLEASE ADD TO GAS NOTES, WELDER | | | CERTIFICTIONS ARE REQUIRED WHEN GAS | | | PERMIT IS APPLYIED FOR. | | | GAS PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|