| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} SUBMIT MANUFACTURERS SPECIFICATIONS |
| | FOR THE GENERATOR AND THE TRANSFER |
| | SWITCH. PLEASE NOTE THE TRANSFER SWITCH |
| | MUST BE SERVICE RATED(225.36) AND MUST |
| | BE CAPABLE OF DISCONNECTING ALL CIRCUITS |
| | SIMULTANEOUSLY, 230.71. |
| | |
| | 2} WHAT IS THE BOX BEING FED WITH 500MCM |
| | (ON THE RISER) FROM THE BOTTOM OF THE |
| | TRANSFER SWITCH? |
| | |
| | 3} THE WASHER, DRYER, HOT TUB/SPA, |
| | ELEVATOR,POOL PUMP AND POOL HEATER, ARE |
| | NOT IN THE LOAD CALCS. |
| | |
| | 4} PLEASE INDICATE THE FEEDER TAP |
| | CONDUCTOR SIZES(LEAVING THE GUTTER). |
| | |
| | 5} THE SMOKE DETECTORS ARE REQUIRED TO |
| | BE INTERCONNECTED PER 905.2.1 FBC. THEY |
| | ARE SHOWN ON TWO DIFFERENT CIRCUITS ON |
| | THE PLAN. ALSO PLEASE NOTE THEY MUST BE |
| | ARC FAULT PROTECTED PER 210.12. THIS |
| | DOES NOT MEAN THEY MUST BE ON A BEDROOM |
| | CIRCUIT NECESSARILY. |
| | |
| | 6} THE ELEVATOR RECEPTACLE AND LIGHT |
| | MUST BE ON A SEPERATE BRANCH CIRCUIT PER |
| | 620.23, SEE A-8 CIRCUIT ALSO FEEDS |
| | DINING ROOM LIGHTING. |
| | |
| | 7} THE CONDENSING UNIT DISCONNECTS AND |
| | ELECTRIC METER DO NOT APPEAR TO HAVE |
| | CLEARANCE PER 110.26. SHOW THE LOCATION |
| | OF THE REST OF THE SERVICE AND GENERATOR |
| | EQUIPMENT ONPLAN. |
| | |