2005-07-14 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SUBMIT MANUFACTURERS SPECIFICATIONS
 FOR THE GENERATOR AND THE TRANSFER
 SWITCH. PLEASE NOTE THE TRANSFER SWITCH
 MUST BE SERVICE RATED(225.36) AND MUST
 BE CAPABLE OF DISCONNECTING ALL CIRCUITS
 SIMULTANEOUSLY, 230.71.
  
 2} WHAT IS THE BOX BEING FED WITH 500MCM
 (ON THE RISER) FROM THE BOTTOM OF THE
 TRANSFER SWITCH?
  
 3} THE WASHER, DRYER, HOT TUB/SPA,
 ELEVATOR,POOL PUMP AND POOL HEATER, ARE
 NOT IN THE LOAD CALCS.
  
 4} PLEASE INDICATE THE FEEDER TAP
 CONDUCTOR SIZES(LEAVING THE GUTTER).
  
 5} THE SMOKE DETECTORS ARE REQUIRED TO
 BE INTERCONNECTED PER 905.2.1 FBC. THEY
 ARE SHOWN ON TWO DIFFERENT CIRCUITS ON
 THE PLAN. ALSO PLEASE NOTE THEY MUST BE
 ARC FAULT PROTECTED PER 210.12. THIS
 DOES NOT MEAN THEY MUST BE ON A BEDROOM
 CIRCUIT NECESSARILY.
  
 6} THE ELEVATOR RECEPTACLE AND LIGHT
 MUST BE ON A SEPERATE BRANCH CIRCUIT PER
 620.23, SEE A-8 CIRCUIT ALSO FEEDS
 DINING ROOM LIGHTING.
  
 7} THE CONDENSING UNIT DISCONNECTS AND
 ELECTRIC METER DO NOT APPEAR TO HAVE
 CLEARANCE PER 110.26. SHOW THE LOCATION
 OF THE REST OF THE SERVICE AND GENERATOR
 EQUIPMENT ONPLAN.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW