Plan Review Notes
Plan Review Notes For Permit 05061669
Permit Number 05061669
Review Stop P
Sequence Number 5
Notes
Date Text
2007-07-09 18:32:27DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEWS: THE COMMENT NUMBER SHALL REMAIN
 THE SAME TO AVOID CONFUSION.
 ******FROM PREVIOUS REVIEWS:
  
 1. ADDRESSED
 2. OK
  
 3. CONTACT DEPT OF BUSINESS REGULATION HOTEL &
 RESTAURANT DIVISION. PROVIDE THEIR COMMENT SHEET AND
 TWO SETS OF STAMPED PLANS. NO COMMENT, WORK SHEETSNOT
 INCLUDED.
 ****RESONSE NOTED, BUT ONE STAMPED SHEET FROM DBPR WITH
 THE TWO PAGE "WORKSHEETS" ATTACHED SHALL BE SUBMITTED
 IN EACH SET OF PLANS. SECTION 101.4.7.-ONLY ONE
 STAMPED SHEET HAS BEEN SUBMITTED, AND THAT IS ON AN OLD
 SET OF PLANS THAT WILL NOT BE APPROVED. PLEASE COMPLY
 WITH REQUIRED STAMPED PAGES AND "WORKSHEETS".
 ******RESPONSE NOTED, BUT THE DBPR FOOD SERVICE STAMP
 IS NOT ON THE MOST RECENT SET OF PLAN AS WELL AS THE
 "WORKSHEETS" AS REQUESTED.
  
 4. ADDRESSED
  
 5. PROVIDE A WATER RISER ISOMETRIC SHOWING ALL FIXTURE
 CONNECTIONS. BACKFLOW PREVENTER REQUIRED AT WATER
 METER.
 ****RESPONSE NOTED, BUT THE WATER ISOMETRIC DOES NOT
 REFLECT THE FLOOR PLAN. RISER INDICATES A BACKFLOW
 PREVENTER AND ALSO A BACKFLOW. PLEASE CLARIFY. -THE
 RISER SHOWS 3 W/C'S & 4 LAVS, WHEREAS THE FLOOR PLAN
 ONLY SHOWS TWO W/C'S AND TWO LAV'S.-THE MOP SINK IS
 NOT INDICATED ON THE RISER.-THE W/C & LAV IN THE
 SECOND TOILET ROOM ARE NOT SHOWN IN THE SAME ORDER ON
 THE RISER DIAGRAM AS SHOWN ON THE PLUMBING PLAN, (FLOOR
 PLAN).-PLEASE IDENTIFY ALL FIXTURES ON THE WATER
 RISER ISOMETRIC DIAGRAM. SECTION 104.2.1.
 ******RESPONSE NOTED, BUT THE RISER DIAGRAM STILL DOES
 NOT REFLECT THE FLOOR PLAN. THE LAVS AND W/CS ARE BACK
 TO BACK IN SEPARATE TOILET ROOMS, NOT LINED UP ON ONE
 COMMON WALL. ALSO AS DRAWN, THE WATER SUPPLY IS
 INSTALLED UNDERGROUND AND THE WATER STUBBED UP THROUGH
 THE FLOOR. THIS WORKS EXCEPT FOR THEWATER HEATER
 WHICH IS IN A LOFT ABOVE THE COOLER/FREEZER. AS DRAWN
 THE WATER HEATER WOULD BE BELOW GROUND. A RISER TO THE
 LOFT FOR THE WATER HEATER IS REQUIRED TO REFLECT THE
 FLOOR PLAN.
  
 6. NEW COMMENT PLUMBING ISOMETRIC DOES NOT MATCH THE
 FLOOR PLAN..
 ****RESPONSE NOTED, BUT THE SANITARY RISER ISOMETRIC
 DIAGRAM STILL DOES NOT REFLECT THE FLOOR PLAN. THE
 FLOOR SINK FOR THE ICE MAKER IS SHOWN CONNECTING TO THE
 GREASE SYSTEM ON THE FLOOR PLAN, BUT IS SHOWN ON THE
 SANITARY SYSTEM ON THE RISER DIAGRAM.-THREE FLOOR
 DRAINS AND ONE HAND SINK ARE ON A SEPARATE BRANCH LINE
 ON THE FLOOR PLAN, BUT ARE ON THE SAME BRANCH LINE WITH
 THE THREE COMPARTMENT SINK ON THE RISER DIAGRAM.- THE
 MOP SINK IS SHOWN BY THE THREE COMPARTMENT SINK ON THE
 RISER DIAGRAM, BUT SHOWN BY THE TOILET ROOMS ON THE
 FLOOR PLAN.-IDENTIFY ALL FIXTURES ON THE RISER
 DIAGRAM AND CORRELATE ALL INFORMATION BETWEEN THE FLOOR
 PLAN AND THE RISER DIAGRAM.-SHOW ALL PIPE SIZES.-
 (SEE ATTACHED SHEET FOR AN EXAMPLE OF A RISER DIAGRAM
 THAT REFLECTS THE FLOOR PLAN AND MEETS CODE
 REQUIREMENTS).
 ******RESPONSE NOTED, BUT THE RISER DIAGRAM STILL DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE
 REQUIREMENTS. THE RISER DIAGRAM SHOWS 2 EXTRA LAVS NOT
 SHOWN ON THE FLOOR PLAN.--THE BRANCH LINES
 INDICATED ON THE FLOOR PLAN ARE NOT REFLECTED ON THE
 RISER DIAGRAM AS INDICATED PREVIOUSLY. --THERE ARE
 TWO DRAIN LINES CONNECTING TO THE FLOOR SINK IN THE
 WAITRESS STATION.--THE MOP SINK SHALL BE VENTED.
 SECTIONS 106.1.1, 1002.1. THE RISER DIAGRAM SENT AS AN
 EXAMPLE WAS NOT REFERENCED WHEN REDRAWING THE SANT.
 RISER DIAGRAM.
  
 7. SHT 2, NOTES FROM PREVIOUS PLAN REVIEWER, JOHN LEECH
 DENIED
  
 NEW COMMENTS:
  
 1.OK
 2. OK
 3. OK
 4. OK
 5. OK
  
 ************NEW COMMENTS************
  
 1C. SHT P-1 SUBMIT CALCULATIONS FOR THE WATER PIPE
 SIZING PER SECTION 604.3.
 ******RESPONSE NOTED, BUT NO CALCULATIONS WERE FOUND ON
 SHT P-1.
  
 2C. OK
  
 3C. SHT P-1 THE FLOOR DRAIN LOCATED WITHIN THE WALK IN
 COOLER SHALL BE INDIRECTLY CONNECTED TO THE SANITARY
 SYSTEM BY AN AIR GAP. SECTION 802.1.2.
 ******RESPONSE NOTED, BUT IT STILL APPEARS TO BE
 CONNECTED DIRECTLY TO THE FLOOR SINK. PLEASE SUBMIT A
 DETAIL SHOWING THE INDIRECT WAST CONNECTION TO THE
 FLOOR SINK AS WELL AS THE REQUIRED 4" AIR GAP.
  
 4C. SEE ATTACHED SHEET CONCERNING THE DESIGN
 PROFESSIONAL AND FLORIDA STATUTE 553.80(2)(B). THIS IS
 GIVEN AS A ONE TIME NOTICE.
 ******A FOUR TIMES THE FEE WOULD HAVE BEEN ASSESSED
 THIS TIME, BUT THE ELECTRICAL PLAN REVIEWER HAS
 ASSESSED THE FEE. IF THE PLANS ARE SUBMITTED AGAIN AND
 THE SAME COMMENTS ARE STILL NOT ADDRESSED, THEN ANOTHER
 FOUR TIMES THE FEE WILL BE ASSESSED.
  
 ************NEW COMMENT************
  
 1D. THERMAL EXPANSION CONTROL IS REQUIRED PER SECTION
 607.3.2. INDICATE THE METHOD OF COMPLIANCE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]