Plan Review Notes
Plan Review Notes For Permit 05061669
Permit Number 05061669
Review Stop E
Sequence Number 5
Notes
Date Text
2007-06-24 10:00:02 
 *** UNSAT 5TH REVIEW***
  
 ** PLEASE SEE THERE ARE STILL MANY ITEMS FROM PREVIOUS
 REVIEWS WHICH STILL NEED TO BE ADDRESSED.
 PLEASE ALSO SEE SOME NEW NOTES AS SOME INFORMATION HAS
 BEEN ADDED TO PLANS AND SOME INFORMATION ON PREVIOUS
 PLANS AHS NOW BEEN REMOVED.
  
  
 1) NOTE: PLEASE BE SURE PLANS CONTAIN ALL THE RELEVANT
 CODES AND YEARS IN WHICH THE PLANS ARE DESIGNED UNDER.
 THIS WAS NOT DONE IN FACT THE PLANS STILL STATE THE
 2004 FBC WHICH THIS PROJECT IS NOT PERMITTED UNDER.
 PLEASE SEE THE MISPRINTS FOR THE NFPA AND NEC.
 PLEASE SEE COMMENT FOR LOAD CALCULATIONS AS CODE(S)
 STATED ARE NOT FROM THE 2002 NEC WHICH IS WHAT THIS
 PROJECT IS PERMITTED UNDER.
  
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY ANY
 OTHER TRADE.
 ** THIS IS UNDER THE 2001 FBC \
 THE FOLLOWING MINIMUM CODES SHALL BE SHOWN ON PLANS
 WHICH ARE RELEVANT TO THE DESIGN OF PROJECT.
 2001 FBC, 2002 NFPA-70(NEC), 2003 NFPA-101, 2002
 NFPA-72 (WHERE APPLICABLE).
  
 2) NOTE: THIS IS THE SAME COMMENT AS PREVIOUS REVIEW.
 PLEASE SEE PLANS STILL ARE MISSING MANY ITEMS NOT
 CIRCUITED. PLEASE SEE SEVERAL LIGHTS WHICH ARE SHOWN ON
 E-2 BUT NOT ON LIGHTING PLANS ON FIRST FLOOR AND NO
 CIRCUITING FOR ANY OF THESE. PLEASE SEE COMMENT FOR
 EMERGENCY LIGHTS ETC.
  
 **PREVIOUS REVIEW NOTE**
 PLEASE SHOW AND COMPLETE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL SCHEDULE. THIS WAS
 STILL NOT DONE; THERE ARE SEVERAL ITEMS ON PLANS WHICH
 DO NOT CONTAIN CIRCUITS. PLEASE ALSO SEE CIRCUIT(S) ON
 PLANS WHICH DO NOT GO TO ANYTHING? PLEASE SEE THAT THE
 PANEL SCHEDULE SHALL BE SPECIFIC TO ALL CIRCUITS AND
 AREAS WHICH THEY FEED. PLEASE BE SURE THE CIRCUITS ON
 SCHEDULE CORRELATES TO THE PLANS FOR ANY ROOM AND AREA
 DESIGNATIONS. THIS REQUIRES THAT THE IDENTIFICATION FOR
 EVERY CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD
 BE LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.
 FBC104.3.1.1 ADMIN SECT 2001.
 NEC 408.4, 240.4, 310.16
  
 3) NOTE:THIS NOTE REMAINS AS CIRCUITING HAS NOT BEEN
 COMPLETED ON PLANS AND REVIEW FOR COMPLIANCE CAN NOT BE
 DONE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 700.12F AS THE EM AND EXT LTS SHALL BE
 CIRCUITED TO THE BRANCH CIRCUIT LIGHTING IN ANY ONE
 AREA WHERE THESE FIXTURES ARE LOCATED.
 PLEASE ALSO SEE COMMENT WITH RESPECT TO FIXTURES AND
 TYPES.
 THIS COMMENT WAS MADE ON PREVIOUS REVIEW FOR
 CIRCUITING.
  
 4) NOTE:PLEASE SEE THE LOAD CALCULATIONS AS SUBMITTED
 ARE NOT CORRECT. PLEASE SEE THE 2002 NEC AND SHOW LOAD
 CALCULATIONS PER NEC. THE LOAD CALCULATIONS AS SHOWN DO
 NOT COORDINATE WITH THE NEC. PLEASE SEE THE NEC HAS
 SEVERAL EXAMPLES WHICH CAN BE USED.
 PLEASE SEE THE SHOW WINDOW LOADS DO NOT SEEM TO
 CORRELATE.
 PLEASE SEE THE INCORRECT CODE IS BEING QUOTED. (SHOULD
 BE 2002 NEC).
 PLEASE SEE NOT ALL CONTINUOUS LOADS ARE SHOWN AT 125%.
  
 *PREVIOUS REVIEW NOTE **
 PLEASE SHOW LOAD CALCULATIONS, WHICH ARE IN COMPLIANCE
 WITH THE 2002 NEC SECTION. 220.
 THIS WAS NOT DONE; THE CALCULATIONS SUBMITTED ARE NOT
 CODE COMPLIANT IN ANY FASHION.
 PLEASE INDICATE HOW LOADS WERE DERIVED ON A LOAD
 SUMMARY BASED FROM THE NEC. 220.
 220.3,220.10,220.11,220.12 220.13, ALL CONTINUOUS LOADS
 125% PER 215.3, 230.42 AND LARGEST MOTOR LOAD. PLEASE
 INCLUDE ALL EXISTING LOADS WITH NEW LOADS BEING ADDED.
 WHERE IS THE REST OF THE SERVICE FOR BUILDING WHICH
 THIS TENANT IS BEING ADDED TO EXISTING???
  
 5) NOTE: THIS NOTE IS THE SAME. THE RESPONSE MENTIONS
 THERE IS SITE/PUBLIC LIGHTING WHICH PROVIDES THE
 LIGHTING, HOWEVER IT IS NOT PERMITTED TO RELY ON THE
 PUBLIC LIGHTING AND QUOTING THE CODE ON PLANS FOR THE
 CONTRACTOR TO PROVIDE THIS IN LIEU OF SHOWING THE
 REQUIRED MINIMUM LEVELS IS NOT PERMITTED.
 PLEASE SEE EMERGENCY LIGHTING ON PLANS WHICH DO NOT
 INDICATE CIRCUITS, FIXTURES WHICH ON FIXTURE LEGEND
 ONLY INDICATES BEING AN EXIT LIGHT AND NOT A
 COMBINATION UNIT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARIFY MEANS OF EGRESS LIGHTING REQUIRED FOR
 REAR OF BLDG TO THE PUBLIC RIGHT OF WAY. THIS INCLUDES
 A BACK UP FIXTURE OF SOME TYPE. A NOTE ON PLANS WHICH
 MENTIONS LIGHTING TO BE INSTALLED DOES NOT COMPLY WITH
 SHOWING THE MINIMUM AS REQUIRED IN DESIGN. LS 101 2003,
 7.8.1.3, 7.9.2.2. PLEASE KNOW, A MIN OF 10FT CANDLES IS
 REQUIRED UNDER NORMAL AND 1FT CANDLE UNDER EM
 CONDITIONS. PLEASE SHOW.
  
 6) NOTE: PLEASE SEE THE PREVIOUS PLANS SUBMITTED THE
 ELECTRICAL RISER AS NEEDED HOWEVER THERE WERE SEVERAL
 ITEMS WHICH WERE NOT NEC COMPLIANT. PLEASE SEE THE
 PLANS ARE NOW MISSING THE RISER ALL TOGETHER?? PLEASE
 SUBMIT A COMPLETED ELECTRICAL RISER DIAGRAM NEW OR
 EXISTING WHICH IS CODE COMPLIANT.
  
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NEW RISER SUBMITTED WHICH IS NOT CODE
 COMPLIANT.
 PLEASE SEE THE SERVICE ENTRANCE CONDUCTOR SIZES ALONG
 WITH FEEDERS ARE NOT OF SUFFICIENT SIZE TO CONFORM TO
 NEC 310.16.
 PLEASE SEE SOME OF THE CONDUCTOR SIZES AS SHOWN ARE NOT
 A STANDARD CONDUCTOR SIZE FROM THE STANDARDS OF AWG
 (AMERICAN WIRE GAUGE) OR NEC 310.16.
 PLEASE SEE SOME OF THE CONDUCTORS ARE ONLY RATED FOR
 200AMPS.
 PLEASE SEE NOTE WHICH MENTIONS *TO PANEL POLE* ? WHAT
 IS THIS?
 PLEASE COMPLETE CONDUCTORS IN GUTTER AND THE REST OF
 THE SERVICE. PLEASE SHOW ON PLANS.
 PLEASE INDICATE SIZE OF METER CAN/SERVICE BEING
 PROVIDED. PLEASE SEE NOTE #4 ABOVE.
  
 ? PLEASE SEE 240.4, 230.2, 110.26, 240.24, 408.7,
 215.5, 230.70, 240.6, ETC.
 ? THERE ARE TOO MANY SECTIONS TO LIST.
  
  
 7) NOTE:AS NOT RISER WAS SUBMITTED REVIEW FOR THIS
 PREVIOUS NOTE CAN NOT BE DONE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING EQUIPMENT GROUNDING CONDUCTOR AFTER
 THE FIRST MEANS OF DISCONNECT. AS THE SERVICE SHOWN IS
 NOT CLEAR FOR THE REST OF THE SERVICE, IT IS UNCLEAR
 WHAT AND WHERE EQUIPMENT GROUNDS ARE FOR THE SERVICE
 AND HOW THEY ARE TO BE INSTALLED AS NOT OTHER EQUIPMENT
 IS BEING SHOWN FOR THE SERVICE. PLEASE SEE 250.66,
 250.6, 250.24B, 250.110, 250.50, 250.104
 AS THE GROUNDING ELECTRODE SYSTEM IS NOT COMPLETE AT
 THIS TIME.
  
 8) NOTE:PLEASE SEE THAT THE LIGHTING FIXTURES ON
 PLANS DO NOT CORRELATE WITH THE FIXTURE LEGEND
 PROVIDED. PLEASE SEE THE FIXTURE LEGEND DOES NOT
 PROVIDE ANY FIXTURE INFORMATION. PLEASE SEE THE PLANS
 DO NOT LABEL LIGHTS FOR TYPE OR EVEN AN ALPHA/NUMERIC
 DESIGNATION WHICH CORRELATES TO THE FIXTURE LEGEND??
 MANY ITEMS FOR REVIEW OF CODE COMPLIANCE NEED TO BE
 DONE.
 **PREVIOUS REVIEW NOTE**
 PLEASE PROVIDE AND A SYMBOL/FIXTURE LEGEND. UNABLE TO
 REVIEW FIXTURES FOR EM / EXT, ARE THESE COMBO UNITS??
  
 9) NOTE: THIS WAS NOT DONE. RESPONSE MENTIONS TO SEE
 PICTURES, HOWEVER NOT PICTURES WERE LOCATED AND PLANS
 STILL ARE REQUIRED TO SHOW THIS.
 110.26, 408.7, 240.24 ETC.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SHOW LOCATION OF THE EXISTING SERVICE. PLEASE
 ALSO SHOW AND INDICATE THE LOAD ON THE EXISTING SERVICE
 WITH NEW LOAD ADDED. AS NOTED ABOVE IN NOTE #4 AND NOTE
 #6.
 220 NEC
 FBC ADMIN SECT 104.3.1.1
  
 10) NOTE: PLEASE SEE THE PLANS NOW INDICATE THE CU AND
 DISCONNECT FOR THE UNIT ON THE SIDE OF BUILDING. THE
 PLANS ALSO STATE ON THE ROOF WHICH BY REVIEW OF PLANS
 PLACES THIS UNIT ON THE ROOF WHICH IS NOT PART OF THIS
 BUILDING. THIS UNIT MAY NOT BE LOCATED ON ADJACENT
 PROPERTY/BUILDING ROOF. AS THE UNIT HAS STILL NOT BEEN
 SHOWN ON PLANS FOR LOCATION AND IT SEEMS THE UNIT COULD
 BE LOCATED ON A SEPARATE PROPERTY FURTHER INFORMATION
 IS NEEDED.
 440.11, 110.26, ETC.
  
 11) NOTE:PLEASE SEE NOT ENERGY CALCULATIONS WERE
 SUBMITTED AND THE RESPONSE WAS THAT THESE ARE NOT
 NEEDED. PLEASE SEE THAT ANY CHANGE IN OCCUPANCY
 REQUIRES COMPLIANCE NOT ONLY WITH CHAPTER 13 OF THE FBC
 BUT ALL ELECTRICAL TECHNICAL CODES.
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE THAT THIS BEING A CHANGE IN OCCUPANCY;
 PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS WHICH COMPLY
 WITH THE 2001 FBC CHAPTER 13.
 THIS WAS NOT SUBMITTED AS REQUIRED PER 415.ABCD AND
 415.2 ETC.
  
 12) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 PLEASE SEE AS SEVERAL COMMENTS STILL REMAIN A 4X FEE
 FOR THE PLAN REVIEW PORTION OF THE BASE PERMIT FEE HAS
 BEEN ASSESSED. THE AMOUNT OF $1080.00 WILL BE DUE UPON
 RE-SUBMITTAL OF THE PLANS. THIS FEE IS THE
 RESPONSIBILITY OF THE DESIGNER OF RECORD AND NOT THE
 CONTRACTOR OR OWNER AS STATED IN THE FLORIDA STATUTES.
 ** PLEASE KNOW THAT ONE SET OF PLANS ARE BEING RETAINED
 AND WILL BE PLACED WITH PREVIOUSLY RETAINED PLANS.
  
 13) NOTE: PLEASE SEE THE APPLIED VALUE FOR THE COMPLETE
 SCOPE OF WORK INCLUDING ALL LABOR, MATERIALS,
 PERMANENTLY INSTALLED EQUIPMENT; DESIGN COST FOR PLANS
 IS LOW. THIS IS REQUIRED WHETHER OR NOT ANY OF THESE
 ITEMS ARE OWNER SUPPLIED.
 PLEASE SEE 104.6.5 UNDER THE 2001 FBCADMIN SECTION AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]